Operational analysis of a newly untreated sewage source heat pump with a plate heat exchanger

被引:4
作者
Qin, Na [1 ]
Tian, He [1 ]
机构
[1] Tianjin Univ Technol, Tianjin Key Lab Adv Mechatron Syst Design & Intel, Natl Demonstrat Ctr Expt Mech & Elect Engn Educ, Sch Mech Engn, Tianjin 300384, Peoples R China
关键词
Untreated sewage source heat pump; Spiral-flow type filter; Plate sewage heat exchanger; Sewage velocity; Heat transfer coefficient; RECOVERY; PERFORMANCE; SYSTEM; TECHNOLOGIES; HYDROCYCLONE; NETWORKS; RETROFIT; FUTURE; BIOGAS;
D O I
10.1007/s00231-021-03141-7
中图分类号
O414.1 [热力学];
学科分类号
摘要
Urban untreated sewage is widely used as a heat source in the heat pump system. Sewage energy has typically been extracted indirectly, i.e., by setting up a heat exchanger before the units. Among sewage heat exchangers, the shell-and-tube heat exchanger is widely applied, while the untreated sewage source heat pump system using a plate heat exchanger is less common owing to its special structure requiring a higher quality of sewage treatment and a superior cleaning method. To solve this problem, a specially designed, sewage source heat pump system was developed and tested. It consists of a kind of pretreatment device, i.e. self-designed spiral-flow type sewage filter and automatic backwashing plate sewage heat exchanger. The model of the heat transfer coefficient of the plate heat exchanger is validated through the comparison between the actual operation data and the theoretical value, and then the influence of the sewage flow velocity on the exchanger is analyzed. Finally, the COP value is calculated, and an energy conservation performance evaluation of the complete system is performed. The test results of actual operation show that the COP value of the new sewage source heat pump system proposed in this paper is 3.02. The filter device has good anti-clogging effect, and the heat exchanger runs stably, achieving the expected energy saving effect.
引用
收藏
页码:683 / 693
页数:11
相关论文
共 35 条
[21]   Raw-water source heat pump for a vertical water treatment building [J].
Oh, Sunhee ;
Cho, Yong ;
Yun, Rin .
ENERGY AND BUILDINGS, 2014, 68 :321-328
[22]   Investigation of the effect of the water phase in the evaporator inlet on economic performance for an Organic Rankine Cycle (ORC) based on industrial data [J].
Ozdil, N. Filiz Tumen ;
Segmen, M. Ridvan .
APPLIED THERMAL ENGINEERING, 2016, 100 :1042-1051
[23]  
Qian Jianfeng Wu., 2007, FLUID MACHINERY, V35, P74
[24]   Experimental investigation on a novel sewage-resource-based system with functions of heat recovery and water purification [J].
Shen, Chao ;
Wang, Mohong ;
Zhang, Chunxiao ;
Dong, Yu ;
Ni, Long ;
Jiang, Yiqiang .
APPLIED THERMAL ENGINEERING, 2020, 165
[25]   An experimental comparison of two heat exchangers used in wastewater source heat pump: A novel dry-expansion shell-and-tube evaporator versus a conventional immersed evaporator [J].
Shen, Chao ;
Jiang, Yiqiang ;
Yao, Yang ;
Wang, Xinlei .
ENERGY, 2012, 47 (01) :600-608
[26]   Experimental study on performance of a de-foulant hydrocyclone with different reflux devices for sewage source heat pump [J].
Song, Tao ;
Tian, Jinyi ;
Ni, Long ;
Shen, Chao ;
Yao, Yang .
APPLIED THERMAL ENGINEERING, 2019, 149 :354-365
[27]   MINLP retrofit of heat exchanger networks comprising different exchanger types [J].
Sorsak, A ;
Kravanja, Z .
COMPUTERS & CHEMICAL ENGINEERING, 2004, 28 (1-2) :235-251
[28]   Optimal number of energy generators for biogas utilization in wastewater treatment facility [J].
Tsagarakis, Konstantinos P. .
ENERGY CONVERSION AND MANAGEMENT, 2007, 48 (10) :2694-2698
[29]   THE PLACEMENT OF 2-STREAM AND MULTI-STREAM HEAT-EXCHANGERS IN AN EXISTING NETWORK THROUGH PATH-ANALYSIS [J].
VANREISEN, JLB ;
GRIEVINK, J ;
POLLEY, GT ;
VERHEIJEN, PJT .
COMPUTERS & CHEMICAL ENGINEERING, 1995, 19 :S143-S148
[30]   Experimental performance analysis of an improved multifunctional heat pump system [J].
Wang, Handong ;
Wang, Qin ;
Chen, Guangming .
ENERGY AND BUILDINGS, 2013, 62 :581-589