Power Quality Phenomena, Standards, and Proposed Metrics for DC Grids

被引:37
作者
Mariscotti, Andrea [1 ]
机构
[1] Univ Genoa, Dept Elect Elect & Telecommun Engn & Naval Archit, I-16145 Genoa, Italy
关键词
DC grid; distortion; electromagnetic compatibility; inrush; microgrid; power quality; pulsed power loads; resonance; ripple; supraharmonics; transients; LOW-FREQUENCY OSCILLATIONS; VOLTAGE; RIPPLE; PROTECTION; CONVERTERS; SYSTEM; AC; SUPERCAPACITORS; MICROGRIDS; MITIGATION;
D O I
10.3390/en14206453
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This work addresses the problem of power quality (PQ) metrics (or indexes) suitable for DC grids, encompassing low and medium voltage applications, including electric transports, all-electric ships and aircrafts, electric vehicles, distributed generation and microgrids, modern data centers, etc. The two main pillars on which such PQ indexes are discussed and built are: (i) the physical justification, so the electric phenomena affecting DC grids and components (PV panels, fuel cells, capacitors, batteries, etc.), causing, e.g., stress of materials, aging, distortion, grid instability; and (ii) the existing standardization framework, pointing out desirable coverage and extension, similarity with AC grids standards, but also inconsistencies. For the first point, each phenomenon is discussed with quantitative conclusions on relevant thresholds: in many cases some percentage of distortion (ripple) is acceptable (stress on capacitors and storage, impact on fuel cells, and PV panels), whereas in other cases, much higher levels may be tolerated (interference to protection and monitoring devices). Standards are reviewed for indications not only of low-order harmonics and voltage fluctuations typical of old DC grid schemes, but also for high-frequency noise, including thus supraharmonics and common-mode disturbance, and filling the gap with the electromagnetic compatibility domain. However, phenomena typical of EMC and electrical safety (such as various types of overvoltages and fast transients) are excluded. Suitable PQ indexes are then reviewed, suggesting integrations and modifications, to cover the relevant phenomena and technological progress, and to better follow the normative exigencies: ripple is considered in time and frequency domain, in particular with a band limited implementation; for transients and pulsed loads, more traditional indexes based on area, energy, and half duration are confronted with indexes evaluating the power trajectory and its derivative.
引用
收藏
页数:41
相关论文
共 150 条
[1]   Integration of PV and Battery Storage for Catenary Voltage Regulation and Stray Current Mitigation in MVDC Railways [J].
Aatif, Salman ;
Yang, Xiaowei ;
Hu, Hai ;
Maharjan, Santa Kumar ;
He, Zhengyou .
JOURNAL OF MODERN POWER SYSTEMS AND CLEAN ENERGY, 2021, 9 (03) :585-594
[2]   Analysis and mitigation of low-frequency oscillations in hybrid AC/DC microgrids with dynamic loads [J].
Ahmed, Moudud ;
Meegahapola, Lasantha ;
Vahidnia, Arash ;
Dattal, Manoj .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2019, 13 (09) :1477-+
[3]  
Albertsen A., 2010, ELECTROLYTIC CAPACIT
[4]   Understanding the Origin of Oscillatory Phenomena Observed Between Wind Farms and HVdc Systems [J].
Amin, Mohammad ;
Molinas, Marta .
IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, 2017, 5 (01) :378-392
[5]   Voltage Differential Protection for Series Arc Fault Detection in Low-Voltage DC Systems [J].
Ananthan, Sundaravaradan Navalpakkam ;
Feng, Xianyong ;
Penney, Charles ;
Gattozzi, Angelo ;
Hebner, Robert ;
Santoso, Surya .
INVENTIONS, 2021, 6 (01) :1-12
[6]  
[Anonymous], 2014, 61000419 IEC
[7]  
[Anonymous], 2014, 6100045 IEC
[8]  
[Anonymous], 2015, MILSTD461 US DEP DEF
[9]  
[Anonymous], 2017, Electric Vehicle Conductive Charging System
[10]  
[Anonymous], 2019, 6100033 IEC