Diagnosis and Location of Power Cable Faults Based on Characteristic Frequencies of Impedance Spectroscopy

被引:9
作者
Li, Gen [1 ]
Chen, Jie [2 ]
Li, Hongze [3 ]
Hu, Libin [2 ]
Zhou, Wenjun [1 ]
Zhou, Chengke [1 ,4 ]
Li, Mingzhen [1 ,5 ]
机构
[1] Wuhan Univ, Sch Elect Engn & Automat, Wuhan 430072, Peoples R China
[2] State Grid Jiangsu Elect Power Co, Elect Power Res Inst, Nanjing 211103, Peoples R China
[3] State Grid Jiangsu Elect Power Co, Nanjing 211103, Peoples R China
[4] Glasgow Caledonian Univ, Sch Comp Engn & Built Environm, Glasgow G4 0BA, Lanark, Scotland
[5] Nantong Univ, Sch Elect Engn, Nantong 226019, Peoples R China
关键词
power cables; aging; deterioration; diagnosis; location; impedance spectroscopy; CROSS-BONDED CABLES;
D O I
10.3390/en15155617
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Power cable condition diagnosis and deterioration location rely on signatures of aging characteristics which precede the final breakdown. The purpose of this study was to investigate how to diagnose and locate the aging and/or deterioration of power cables through the analysis of the impedance spectroscopy. The concepts of the reference frequency and characteristic frequency of cable impedance spectroscopy are defined for the first time. Based on the reference frequency, the optimal frequency range for analysis of impedance spectroscopy can be determined, whilst based on characteristic frequency, a set of criteria for assessing cable conditions are examined and established. The solution proposed in this paper has the advantage of being easier to implement than the previously reported "broadband" impedance spectroscopy methods, as it helps to reduce the frequency range for measurement instrumentations; the proposed method also does not need the measurements of the parameters of the cable being tested.
引用
收藏
页数:18
相关论文
共 29 条
[1]   A study of expected lifetime of XLPE insulation cables working at elevated temperatures by applying accelerated thermal ageing [J].
Alghamdi, Abdulsalam S. ;
Desuqi, Rayan K. .
HELIYON, 2020, 6 (01)
[2]   Numerical Modeling of Partial Discharge in a Void Cavity Within High-Voltage Cable Insulation [J].
Algwari, Qais Th ;
Saleh, Dawood N. .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 2021, 49 (05) :1536-1542
[3]  
[Anonymous], 2014, IEC 60287-1-1:2006+A1:2014
[4]   Prediction of dielectric parameters of an aged mv cable: A comparison of curve fitting, decision tree and artificial neural network methods [J].
Arikan, Oktay ;
Uydur, Cihat Cagdas ;
Kumru, Celal Fadil .
ELECTRIC POWER SYSTEMS RESEARCH, 2022, 208
[5]   Online Monitoring and Diagnosis of HV Cable Faults by Sheath System Currents [J].
Dong, Xiang ;
Yang, Yang ;
Zhou, Chengke ;
Hepburn, Donald M. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2017, 32 (05) :2281-2290
[6]   Innovative Development and Application of a Stress-Strength Model for Reliability Estimation of Aged LV Cables for Nuclear Power Plants [J].
Fabiani, D. ;
Mazzanti, G. ;
Suraci, S., V ;
Diban, B. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2021, 28 (06) :2083-2090
[7]   Broadband Dielectric Spectroscopy: A Viable Technique for Aging Assessment of Low-Voltage Cable Insulation Used in Nuclear Power Plants [J].
Fabiani, Davide ;
Suraci, Simone Vincenzo .
POLYMERS, 2021, 13 (04) :1-11
[8]  
Fantoni P.F., 2006, CABLE AGING ASSESSME, V12, P177
[9]   A Techno-Economic Framework for Replacing Aged XLPE Cables in the Distribution Network [J].
Hamad, Amr A. ;
Ghunem, Refat Atef .
IEEE TRANSACTIONS ON POWER DELIVERY, 2020, 35 (05) :2387-2393
[10]   Ultraviolet radiation aging impact on physicochemical properties of crosslinked polyethylene cable insulation [J].
Hedir, Abdallah ;
Moudoud, Mustapha ;
Lamrous, Omar ;
Rondot, Sebastien ;
Jbara, Omar ;
Dony, Philippe .
JOURNAL OF APPLIED POLYMER SCIENCE, 2020, 137 (16)