Computational study of the air flow dynamics in an induced draft cooling tower

被引:5
作者
Velandia, Juan S. [1 ]
Chery, Marie [2 ]
Lopez, Omar D. [1 ]
机构
[1] Univ Los Andes, Dept Mech Engn, Cra 1 Este 19A-40, Bogota, Colombia
[2] Edospina, Cra 7 24-89, Bogota, Colombia
关键词
Computational fluid dynamics; Cooling tower; Air flow dynamics; Porous media modeling; CFD;
D O I
10.1007/s40430-015-0348-y
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
Cooling towers are one of the main solutions to reduce the water temperature used in industrial facilities. The air flow dynamics inside these devices is of especial interest, since it determines important operational variables such as power consumption. The present paper focuses on the air flow dynamics of two different geometrical configurations of induced draft cooling towers: a squared transverse area (referred as "FV25") and a circular transverse area (referred as "FV25c"). The complexity of the flow in some elements of the cooling tower such as the filmic fill and the drift eliminator was simplified by modeling them as porous media. The numerical parameters of the porous media models for these zones were based on detailed simulations of both elements in a wind tunnel-like configuration. Comparison of both configurations of the towers was made in terms of velocity and pressure contours, pressure drop and power consumption. It was found that the power used by the FV25c tower was only 60 % of the power used by the previous FV25 model due to complexity on the flow interaction and sudden transverse section changes. Computational fluid dynamics has proven to be a useful tool for the design process of cooling towers in the Colombian industry, as it allows understanding details of the air flow dynamics inside the cooling tower.
引用
收藏
页码:2393 / 2401
页数:9
相关论文
共 14 条
[1]   CFD simulation of wet cooling towers [J].
Al-Waked, R ;
Behnia, M .
APPLIED THERMAL ENGINEERING, 2006, 26 (04) :382-395
[2]   Evaporative cooling of water in a mechanical draft cooling tower [J].
Fisenko, SP ;
Brin, AA ;
Petruchik, AI .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2004, 47 (01) :165-177
[3]   Aerodynamic analysis and CFD simulation of several cellulose evaporative cooling pads used in Mediterranean greenhouses [J].
Franco-Salas, Antonio ;
Valera, D. L. ;
Pena, A. ;
Perez, A. M. .
COMPUTERS AND ELECTRONICS IN AGRICULTURE, 2011, 76 (02) :218-230
[4]   Application of CFD to closed-wet cooling towers [J].
Gan, G ;
Riffat, SB ;
Shao, L ;
Doherty, P .
APPLIED THERMAL ENGINEERING, 2001, 21 (01) :79-92
[5]   Experimental study on the performance of mechanical cooling tower with two types of film packing [J].
Gharagheizi, Farhad ;
Hayati, Reza ;
Fatemi, Shohreh .
ENERGY CONVERSION AND MANAGEMENT, 2007, 48 (01) :277-280
[6]   The investigation of cooling tower packing in various arrangements [J].
Goshayshi, HR ;
Missenden, JF .
APPLIED THERMAL ENGINEERING, 2000, 20 (01) :69-80
[7]   Numerical simulation of counter-flow wet-cooling towers [J].
Heidarinejad, Ghassem ;
Karami, Maryam ;
Delfani, Shahram .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2009, 32 (05) :996-1002
[8]   Numerical Modelling of Natural Draft Wet-Cooling Towers [J].
Klimanek, Adam .
ARCHIVES OF COMPUTATIONAL METHODS IN ENGINEERING, 2013, 20 (01) :61-109
[9]  
Kloppers J.C., 2003, CRITICAL EVALUATION
[10]   Cooling tower performance evaluation:: Merkel, poppe, and e-NTU methods of analysis [J].
Kloppers, JC ;
Kröger, DG .
JOURNAL OF ENGINEERING FOR GAS TURBINES AND POWER-TRANSACTIONS OF THE ASME, 2005, 127 (01) :1-7