An Experimental Study of Short-Circuit Current Making Operation of Air Medium-Voltage Load Break Switches

被引:5
作者
Dorraki, Naghme [1 ]
Niayesh, Kaveh [1 ]
机构
[1] Norwegian Univ Sci & Technol, Dept Elect Power Engn, N-7491 Trondheim, Norway
关键词
Medium voltage (MV); load break switch (LBS); making operations; contacts erosion; arcing contacts; main contacts; arc erosion; CURRENT INTERRUPTION; CONTACT EROSION; GAS; SF6;
D O I
10.1109/TPWRD.2022.3153237
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Replacing SF6, the most potent greenhouse gas, with an alternative gas is a challenge faced by medium-voltage load break switches (MV-LBS). Air is a possible alternative, but there are some challenges regarding low dielectric strength leading to high arcing time and dissipated energy. Therefore, understanding the switching processes for both interruption and making operations in air MV-LBS is crucial to designing efficient compact switchgear. This work focuses on making operations in air MV-LBS. A synthetic test circuit and a model switch are designed based on the standards to simulate making operations under fault conditions similar to a real test. The test condition is set to achieve high pre-strike arcing time and energy. The results show that the most destructive impact of the making short-circuit current occurs in the first half-cycle of the load current when the pre-strike arc is formed. For an average short-circuit current with a peak of 22 kA and a breakdown voltage of 20 kV, the switch failed to re-open due to the arcing contacts welding after four successive making operations without main contacts and seven successive operations with main contacts. It has been shown that the total arcing contact mass loss occurs mainly during the pre-arcing time.Increasing the closing speed could be a possible solution to minimize the impact of arcing.
引用
收藏
页码:4646 / 4656
页数:11
相关论文
共 23 条
[1]  
[Anonymous], 2021, 62271200 IEC INT
[2]   Online Condition Assessment of Interruption Chamber of Gas Circuit Breakers Using Arc Voltage Measurement [J].
Bagherpoor, Asghar ;
Rahimi-Pordanjani, Sadegh ;
Razi-Kazemi, Ali Asghar ;
Niayesh, Kaveh .
IEEE TRANSACTIONS ON POWER DELIVERY, 2017, 32 (04) :1776-1783
[3]   Design Rules for Environmentally Friendly Medium Voltage Load Break Switches [J].
Bendig, Marvin ;
Schaak, Martin .
IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (05) :2668-2675
[4]   Evaluation method of contact erosion for high voltage SF6 circuit breakers using dynamic contact resistance measurement [J].
Cheng, Tingting ;
Gao, Wensheng ;
Liu, Weidong ;
Li, Ruipeng .
ELECTRIC POWER SYSTEMS RESEARCH, 2018, 163 :725-732
[5]   Optical investigation on pre-strike arc characteristics in medium-voltage load break switches [J].
Dorraki, Naghme ;
Niayesh, Kaveh .
JOURNAL OF PHYSICS D-APPLIED PHYSICS, 2021, 54 (25)
[6]  
Hatziargyriou N., 2020, ELECT SUPPLY SYSTEMS
[7]   Development of a Method of Calculating the Melting Characteristics of OPGW Strands Due to DC Arc Simulating Lightning Strike [J].
Iwata, Mikimasa ;
Ohtaka, Toshiya ;
Kuzuma, Yasukuni ;
Goda, Yutaka .
IEEE TRANSACTIONS ON POWER DELIVERY, 2013, 28 (03) :1314-1321
[8]   Interruption in Air for Different Medium-Voltage Switching Duties [J].
Jonsson, Erik ;
Runde, Magne .
IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (01) :161-166
[9]   SF6-alternative gases for application in gas-insulated switchgear [J].
Li, Xingwen ;
Zhao, Hu ;
Murphy, Anthony B. .
JOURNAL OF PHYSICS D-APPLIED PHYSICS, 2018, 51 (15)
[10]   Heat transfer and cold cathode erosion in electric arc heaters [J].
Marotta, A ;
Sharakhovsky, LI .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 1997, 25 (05) :905-912