Energy performance analysis on telecommunication base station

被引:49
|
作者
Tu, Rang [1 ]
Liu, Xiao-Hua [1 ]
Li, Zhen [1 ]
Jiang, Yi [1 ]
机构
[1] Tsinghua Univ, Dept Bldg Sci, Beijing 100084, Peoples R China
关键词
Telecommunication base station; Cooling load; Envelope; Energy consumption; Air conditioning system;
D O I
10.1016/j.enbuild.2010.09.019
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Telecommunication base station (TBS) has high indoor IT heat dissipation rate, and cooling load exists almost all year around. Energy consumption of air-conditioning system is 30-50% of the TBS entire energy. Envelope and heat pipe assisted air-conditioning system performances are investigated using annual hourly simulation software. In cold city Harbin, high insulation envelope is recommended to avoid heating requirement in winter; and in warm city Guangzhou, low insulation envelope is recommended to reduce the annual cooling load. Shading and roof ventilation have little impact on the reduction of cooling load. Simplified analysis method based on daily average steady values is proposed, which can reveal the main performance influencing factors and clearly direct the main approach in energy saving. The simplified method can accord well with numerical results and tested results available in literature. Contribution of each heat source can be clearly gained and analyzed, solar radiation does not possess large effect in TBS. Ideal thermal resistance with no heating or cooling requirement is then derived, envelope can be easily optimized and contribution of such kind of outdoor cooling source method using heat pipe can be easily obtained. (C) 2010 Elsevier B.V. All rights reserved.
引用
收藏
页码:315 / 325
页数:11
相关论文
共 50 条
  • [1] Energy-saving analysis of telecommunication base station with thermosyphon heat exchanger
    Zhou, Feng
    Chen, Jie
    Ma, Guoyuan
    Liu, Zhongliang
    ENERGY AND BUILDINGS, 2013, 66 : 537 - 544
  • [2] Study on energy efficient envelope design for telecommunication base station in Guangzhou
    Zhang, Yufeng
    Chen, Yi
    Wu, Ji
    Meng, Qinglin
    ENERGY AND BUILDINGS, 2008, 40 (10) : 1895 - 1900
  • [3] Simulation on energy performance of air-conditioning system assisted with thermosyphon used in telecommunication base station
    Zhang, Penglei
    Wang, Baolong
    Shi, Wenxing
    Han, Linjun
    Li, Xianting
    BUILDING SIMULATION 2013: 13TH INTERNATIONAL CONFERENCE OF THE INTERNATIONAL BUILDING PERFORMANCE SIMULATION ASSOCIATION, 2013, : 1548 - 1553
  • [4] Energy-saving and economic analysis of passive radiative sky cooling for telecommunication base station in China
    Zengkai Cui
    Chenyue Guo
    Dongliang Zhao
    Building Simulation, 2022, 15 : 1775 - 1787
  • [5] Energy-saving and economic analysis of passive radiative sky cooling for telecommunication base station in China
    Cui, Zengkai
    Guo, Chenyue
    Zhao, Dongliang
    BUILDING SIMULATION, 2022, 15 (10) : 1775 - 1787
  • [6] A power peak load shifting mixing with solar energy solution for hybrid energy system of the telecommunication base station
    Kong, Weifeng
    Teng, Lingqiao
    Zhang, Shaomin
    Zhang, Dedi
    Liu, Xian
    Shao, Bin
    2018 IEEE INTERNATIONAL TELECOMMUNICATIONS ENERGY CONFERENCE (INTELEC), 2018,
  • [7] Resilience Analysis under the Impact of Cell Failures in the Practical Telecommunication base Station Networks
    Xue, Zongqi
    Liang, Zhenglin
    2022 IEEE 22ND INTERNATIONAL CONFERENCE ON SOFTWARE QUALITY, RELIABILITY, AND SECURITY COMPANION, QRS-C, 2022, : 778 - 779
  • [8] Spatio-Temporal Analysis and Prediction of Mass Telecommunication Base Station Failure Events
    Wu, Tong
    Wang, Yudong
    Ye, Zhi-Sheng
    Chen, Nan
    TECHNOMETRICS, 2024, 66 (01) : 77 - 89
  • [9] Entropy generation rate analysis of a thermosyphon heat exchanger for cooling a telecommunication base station
    Zhou, Feng
    Ma, Guoyuan
    Wang, Shuchun
    INTERNATIONAL JOURNAL OF EXERGY, 2017, 22 (02) : 139 - 157
  • [10] Heat flows and energetic behavior of a telecommunication radio base station
    Petraglia, Antonio
    Spagnuolo, Antonio
    Vetromile, Carmela
    D'Onofrio, Antonio
    Lubritto, Carmine
    ENERGY, 2015, 89 : 75 - 83