Subsynchronous Interaction Between Direct-Drive PMSG Based Wind Farms and Weak AC Networks

被引:534
作者
Liu, Huakun [1 ]
Xie, Xiaorong [1 ]
He, Jingbo [2 ]
Xu, Tao [2 ]
Yu, Zhao [2 ]
Wang, Chao [2 ]
Zhang, Chuanyu [1 ]
机构
[1] Tsinghua Univ, Dept Elect Engn, State Key Lab Power Syst, Beijing 100084, Peoples R China
[2] State Grid Corp China, Beijing 100031, Peoples R China
基金
中国国家自然科学基金;
关键词
Direct-drive permanent magnetic synchronous generator; impedance model; subsynchronous interaction; torsional vibration; wind power; POWER-SYNCHRONIZATION CONTROL; MITIGATING SSR; STABILITY; IMPEDANCE; SYSTEMS;
D O I
10.1109/TPWRS.2017.2682197
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Recently, sustained power oscillation at subsynchronous frequency was captured in direct-drive permanent magnetic synchronous generator (PMSG) based wind farms in Xinjiang Uygur Autonomous Region, China. This new type of subsynchronous interaction (SSI) detected in practical systems has never been reported and analyzed before. Therefore, its mechanism and characteristics are not yet clearly clarified. In this paper, a simplified but representative system model with multiple PMSGs interfaced with AC networks is established first based on the actual system and the PMSG model provided by the manufacturer. Then, small-signal eigenanalysis, time-domain simulation, and impedance model analysis are carried out to investigate the interactive dynamics between them. The results show that such interaction between direct-drive PMSG wind farms and weak ac grids characterized by low short-circuit ratio would cause negative-resistance effect for the SSI mode, leading to unstable oscillation. In such cases, the controller of PMSG would saturate soon, resulting in sustained power oscillation in the system. If unfortunately the oscillation frequency matches the torsional mode of any nearby turbogenerator, severe torsional vibration would be excited on the shaft of the latter. The analysis results are finally validated with field measurements of an actual SSI event. To address the problem, a supplementary subsynchronous damping control loop is attached to the controllers of PMSGs to reshape the impedance and thus to stabilize the SSI.
引用
收藏
页码:4708 / 4720
页数:13
相关论文
共 38 条
[1]  
Adams J., 2012, P TRANSM DISTR C EXP, P1
[2]   Optimal Compensation of Transmission Lines Based on Minimisation of the Risk of Subsynchronous Resonance [J].
Adrees, Atia ;
Milanovic, Jovica V. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2016, 31 (02) :1038-1047
[3]   A Simple Approach to Damp SSR in Series-Compensated Systems via Reshaping the Output Admittance of a Nearby VSC-Based System [J].
Alawasa, Khaled Mohammad ;
Mohamed, Yasser Abdel-Rady I. .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2015, 62 (05) :2673-2682
[4]   Impedance and Damping Characteristics of Grid-Connected VSCs With Power Synchronization Control Strategy [J].
Alawasa, Khaled Mohammad ;
Mohamed, Yasser Abdel-Rady I. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2015, 30 (02) :952-961
[5]   Modeling, Analysis, and Suppression of the Impact of Full-Scale Wind-Power Converters on Subsynchronous Damping [J].
Alawasa, Khaled Mohammad ;
Mohamed, Yasser Abdel-Rady I. ;
Xu, Wilsun .
IEEE SYSTEMS JOURNAL, 2013, 7 (04) :700-712
[6]   Active Mitigation of Subsynchronous Interactions Between PWM Voltage-Source Converters and Power Networks [J].
Alawasa, Khaled Mohammad ;
Mohamed, Yasser Abdel-Rady Ibrahim ;
Xu, Wilsun .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2014, 29 (01) :121-134
[7]  
[Anonymous], 1992, IEEE Transactions on Power Systems, V7, P150, DOI 10.1109/59.141698
[8]  
[Anonymous], POWER SYSTEM STABILI
[9]   Reactance Scan Crossover-Based Approach for Investigating SSCI Concerns for DFIG-Based Wind Turbines [J].
Cheng, Yunzhi ;
Sahni, Mandhir ;
Muthumuni, Dharshana ;
Badrzadeh, Babak .
IEEE TRANSACTIONS ON POWER DELIVERY, 2013, 28 (02) :742-751
[10]   ON THE GENERALIZED NYQUIST STABILITY-CRITERION [J].
DESOER, CA ;
WANG, YT .
IEEE TRANSACTIONS ON AUTOMATIC CONTROL, 1980, 25 (02) :187-196