Partial Discharge-induced Degradation Characteristics of Insulating Structure Constituting Oil-immersed Power Transformers

被引:23
|
作者
Okabe, Shigemitsu [1 ]
Ueta, Genyo [1 ]
Wada, Haruhisa [2 ]
Okubo, Hitoshi [3 ]
机构
[1] Tokyo Elect Power Co Ltd, Tsurumi Ku, Kanagawa 2308510, Japan
[2] Toshiba Co Ltd, Kawasaki Ku, Kanagawa 2100862, Japan
[3] Nagoya Univ, Dept Elect Engn & Comp Sci, Chikusa Ku, Nagoya, Aichi 4648603, Japan
关键词
Oil-immersed power transformer; partial discharge (PD); press-board (PB); insulating element model; residual lightning impulse withstand voltage; harmful partial discharge level; insulation degradation;
D O I
10.1109/TDEI.2010.5595570
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The soundness of an oil-immersed power transformer under an operating voltage is evaluated in partial discharge (PD) test of long-duration ac withstand voltage test. The acceptance criterion for this PD test is 500 pC according to IEC standard; however, only insufficient basic data backing this criterion are available. In addition, the harmful level of the insulation performance has not necessarily been perceived in such a manner as the present one, for example, only the insulation breakdown, instead of the insulation performance degradation, has been assumed to be harmful. In light of the consideration presently paid, it is necessary to determine the PD level that causes the insulation performance to be degraded in order to confirm the soundness by the test using an actual transformer. As the initial step of the study for this purpose, the previous paper investigated the PD and the insulation damage level using oil-impregnated press-boards (PBs) used in the transformer, at which PD is more likely to occur when ac voltage is applied than at any other parts, and evaluated the harmful PD level for insulating materials themselves. To investigate the harmful PD level for the actual transformer, this paper studied the harmful PD level that decreases the residual lightning impulse (LI) withstand voltage using the main insulation model, which is the insulating structure constituting the oil-immersed power transformer. As a result, black discoloration occurred on the surface of the PB and the residual LI withstand voltage also tended to decline when exposed to ac PD of 20,000 pC or more. On the other hand, when it had been exposed to ac PD of 10,000 pC, no visible damage was observed and there was no drop in the residual LI withstand voltage either. Consequently, the harmful ac PD level for the oil-immersed transformer can be determined at between 10,000 pC and 20,000 pC. This result coincided with that for insulating materials themselves, hence it was revealed that the harmful PD level be set to 10,000 pC on a conservative side.
引用
收藏
页码:1649 / 1656
页数:8
相关论文
共 50 条
  • [31] Health status perception of oil-immersed power transformers considering wind power uncertainty
    Yi, Lingzhi
    Su, Xingren
    Wang, Yahui
    Xu, Xunjian
    Liu, Jiangyong
    She, Haixiang
    ELECTRIC POWER SYSTEMS RESEARCH, 2024, 234
  • [32] Effects of Thiophene Degradation on the Corrosiveness of Oil and the Properties of Oil-Paper Insulation in the Oil-Immersed Transformers
    Gao, Sihang
    Feng, Shaoxuan
    Ke, Tingjing
    Chen, Yiduo
    Zeng, Xisong
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2023, 30 (01) : 429 - 438
  • [33] Detection and Analysis of Partial Discharges in Oil-Immersed Power Transformers Using Low-Cost Acoustic Sensors
    Besharatifard, Hamidreza
    Hasanzadeh, Saeed
    Heydarian-Forushani, Ehsan
    Alhelou, Hassan Haes
    Siano, Pierluigi
    APPLIED SCIENCES-BASEL, 2022, 12 (06):
  • [34] On Thermal Performance Analysis of Oil-Immersed Power Transformers: Winding Cooling Curve
    Gamil, A.
    Schluecker, E.
    2022 7TH INTERNATIONAL ADVANCED RESEARCH WORKSHOP ON TRANSFORMERS (ARWTR 2022), 2022, : 1 - 6
  • [35] Electrical insulation diagnostic method and maintenance criteria for oil-immersed power transformers
    Okubo, H.
    Kobayashi, S.
    Aoshima, Y.
    Takagi, H.
    Mori, E.
    Ikeda, M.
    Kishi, A.
    IEEE International Conference on Conduction and Breakdown in Dielectric Liquids, ICDL, 1999, : 372 - 377
  • [36] Kolmogorov-Arnold Network in the Fault Diagnosis of Oil-Immersed Power Transformers
    Cabral, Thales W.
    Gomes, Felippe V.
    de Lima, Eduardo R.
    Filho, Jose C. S. S.
    Meloni, Luis G. P.
    SENSORS, 2024, 24 (23)
  • [37] Analyzing and Comparing Thermal Models of Indoor and Outdoor Oil-Immersed Power Transformers
    Mamizadeh, A.
    Iskender, I.
    2009 IEEE BUCHAREST POWERTECH, VOLS 1-5, 2009, : 3042 - 3049
  • [38] A fast computational method for internal temperature field in Oil-Immersed power transformers
    Liu, Gang
    Hu, Wanjun
    Hao, Shiyuan
    Gao, Chenglong
    Liu, Yunpeng
    Wu, Weige
    Li, Lin
    APPLIED THERMAL ENGINEERING, 2024, 236
  • [39] Fault diagnosis of oil-immersed power transformers using common vector approach
    Kirkbas, Ali
    Demircali, Akif
    Koroglu, Selim
    Kizilkaya, Aydin
    ELECTRIC POWER SYSTEMS RESEARCH, 2020, 184
  • [40] A validated online algorithm for detection of fan failures in oil-immersed power transformers
    Djamali, Mohammad
    Tenbohlen, Stefan
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2017, 116 : 224 - 233