Partial Discharge-induced Degradation Characteristics of Insulating Structure Constituting Oil-immersed Power Transformers

被引:23
|
作者
Okabe, Shigemitsu [1 ]
Ueta, Genyo [1 ]
Wada, Haruhisa [2 ]
Okubo, Hitoshi [3 ]
机构
[1] Tokyo Elect Power Co Ltd, Tsurumi Ku, Kanagawa 2308510, Japan
[2] Toshiba Co Ltd, Kawasaki Ku, Kanagawa 2100862, Japan
[3] Nagoya Univ, Dept Elect Engn & Comp Sci, Chikusa Ku, Nagoya, Aichi 4648603, Japan
关键词
Oil-immersed power transformer; partial discharge (PD); press-board (PB); insulating element model; residual lightning impulse withstand voltage; harmful partial discharge level; insulation degradation;
D O I
10.1109/TDEI.2010.5595570
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The soundness of an oil-immersed power transformer under an operating voltage is evaluated in partial discharge (PD) test of long-duration ac withstand voltage test. The acceptance criterion for this PD test is 500 pC according to IEC standard; however, only insufficient basic data backing this criterion are available. In addition, the harmful level of the insulation performance has not necessarily been perceived in such a manner as the present one, for example, only the insulation breakdown, instead of the insulation performance degradation, has been assumed to be harmful. In light of the consideration presently paid, it is necessary to determine the PD level that causes the insulation performance to be degraded in order to confirm the soundness by the test using an actual transformer. As the initial step of the study for this purpose, the previous paper investigated the PD and the insulation damage level using oil-impregnated press-boards (PBs) used in the transformer, at which PD is more likely to occur when ac voltage is applied than at any other parts, and evaluated the harmful PD level for insulating materials themselves. To investigate the harmful PD level for the actual transformer, this paper studied the harmful PD level that decreases the residual lightning impulse (LI) withstand voltage using the main insulation model, which is the insulating structure constituting the oil-immersed power transformer. As a result, black discoloration occurred on the surface of the PB and the residual LI withstand voltage also tended to decline when exposed to ac PD of 20,000 pC or more. On the other hand, when it had been exposed to ac PD of 10,000 pC, no visible damage was observed and there was no drop in the residual LI withstand voltage either. Consequently, the harmful ac PD level for the oil-immersed transformer can be determined at between 10,000 pC and 20,000 pC. This result coincided with that for insulating materials themselves, hence it was revealed that the harmful PD level be set to 10,000 pC on a conservative side.
引用
收藏
页码:1649 / 1656
页数:8
相关论文
共 50 条
  • [1] Partial Discharge-induced Degradation Characteristics of Oil-impregnated Insulating Material Used in Oil-immersed Power Transformers
    Okabe, Shigemitsu
    Ueta, Genyo
    Wada, Haruhisa
    Okubo, Hitoshi
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (04) : 1225 - 1233
  • [2] Partial Discharge-induced Degradation Characteristics of Insulating Materials of Gas-filled Power Transformers
    Okabe, Shigemitsu
    Ueta, Genyo
    Wada, Haruhisa
    Okubo, Hitoshi
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (06) : 1715 - 1723
  • [3] The effects of insulator structure and insulating oil to charge accumulation in oil-immersed transformers
    Wakamatsu, M
    Kato, K
    Koide, H
    Okubo, H
    PROCEEDINGS OF THE 7TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1-3, 2003, : 483 - 486
  • [5] Effects of Metal Passivator Degradation on the Dissolved Gases Characteristics of Oil in Oil-immersed Transformers
    Gao, Si-hang
    Zeng, Xi-Song
    Zhang, Guo-wen
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2021, 28 (05) : 1735 - 1742
  • [6] Deterioration Characteristics Due to Partial Discharges in Insulating Structure Constituting Gas-filled Power Transformers
    Okabe, Shigemitsu
    Ueta, Genyo
    Wada, Haruhisa
    Okubo, Hitoshi
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (04) : 1204 - 1213
  • [7] Retrofilling Mineral Oil-Immersed Transformers with Alternative Insulating Liquids: A Review
    Montero, Andres
    Garcia, Belen
    IEEE ELECTRICAL INSULATION MAGAZINE, 2024, 40 (06) : 6 - 22
  • [8] Degradation Characteristics of Oil-immersed Pressboard Samples Induced by Partial Discharges under DC Voltage
    Li, Yuan
    Zhang, Qiaogen
    Wang, Tonglei
    Li, Jinzhong
    Guo, Can
    Ni, Heli
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (02) : 1110 - 1117
  • [9] Potential application of palm oil products as electrical insulating medium in oil-immersed transformers
    Mohd, Noor Khairin
    Lim Wen-Huei
    Abu Hassan, Noor Armylisa's
    Shoot-Kian, Yeong
    ENVIRONMENTAL PROGRESS & SUSTAINABLE ENERGY, 2021, 40 (06)
  • [10] Partial Discharge and Deterioration Characteristics of Oil-Immersed Pressboard Under Bubble Defects
    Yang, Chaojie
    Zhao, Tao
    Liu, Yunpeng
    Yang, Jiajun
    Liu, Yijin
    Liu, Yunuo
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2024, 31 (06) : 3453 - 3461