Corrections to the simple effectiveness-NTU method for counterflow cooling towers and packed bed liquid desiccant-air contact systems

被引:43
|
作者
Ren, Cheng-Qin [1 ]
机构
[1] Hunan Univ, Coll Mech & Automot Engn, Changsha 410082, Peoples R China
关键词
cooling towers and liquid desiccant-air contact systems; heat and mass transfer; effectiveness-NTU method; corrections; perturbation technique;
D O I
10.1016/j.ijheatmasstransfer.2007.04.028
中图分类号
O414.1 [热力学];
学科分类号
摘要
Analytical expressions for the corrections to the simple effectiveness-NTU method are developed using perturbation technique for cooling towers and liquid desiccant-air contact systems. The developed model takes into consideration the effect of nonlinearities of humidity ratio and enthalpy of air in equilibrium with water or desiccant solutions. The model also takes into consideration the effect of water loss by evaporation and the effect of variation of the specific heat capacity of water or solution. The comparison with numerical integration of the dimensional heat and mass transfer equations shows that the analytical results are generally satisfactory and the improvement over the simple epsilon-NTU method is significant. (C) 2007 Elsevier Ltd. All rights reserved.
引用
收藏
页码:237 / 245
页数:9
相关论文
共 8 条
  • [1] Effectiveness-NTU relation for packed bed liquid desiccant-air contact systems with a double film model for heat and mass transfer
    Ren, Cheng Qin
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2008, 51 (7-8) : 1793 - 1803
  • [2] Effectiveness-NTU method for design of packed bed liquid desiccant dehumidifiers
    Sadasivam, M.
    Balakrishnan, A.R.
    Chemical Engineering Research and Design, 1992, 70 (A6) : 572 - 577
  • [3] EFFECTIVENESS-NTU METHOD FOR DESIGN OF PACKED-BED LIQUID DESICCANT DEHUMIDIFIERS
    SADASIVAM, M
    BALAKRISHNAN, AR
    CHEMICAL ENGINEERING RESEARCH & DESIGN, 1992, 70 (A6): : 572 - 577
  • [4] Design of Cooling Towers by the Effectiveness-NTU Method
    Jaber, H.
    Webb, R. L.
    JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1989, 111 (1-4): : 837 - 843
  • [5] Simplified analysis of coupled heat and mass transfer processes in packed bed liquid desiccant-air contact system
    Ren, CQ
    Jiang, Y
    Zhang, YP
    SOLAR ENERGY, 2006, 80 (01) : 121 - 131
  • [6] An improved effectiveness-NTU method for streamlining the design and optimization of packed bed latent thermal energy storage
    Tang, Yong
    Wang, Zhichao
    Lyu, Weihua
    SUSTAINABLE CITIES AND SOCIETY, 2024, 100
  • [7] Steady-state performance assessment and geometrical optimization of packed-bed liquid desiccant air dehumidification systems
    Bhowmik, Mrinal
    Gohain, Karanjeet
    Muthukumar, P.
    Saito, Kiyoshi
    THERMAL SCIENCE AND ENGINEERING PROGRESS, 2023, 38
  • [8] Heat and mass transfer performance comparison between a direct-contact liquid desiccant packed bed and a liquid-to-air membrane energy exchanger for air dehumidification
    Ge, Gaoming
    Abdel-Salam, Ahmed H.
    Abdel-Salam, Mohamed R. H.
    Besant, Robert W.
    Simonson, Carey J.
    SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2017, 23 (01) : 2 - 15