Experimental Study on the Detection of Trace H2S and H2O in High

被引:2
作者
Tang, Feng [1 ]
Liu, Shungui [1 ]
Lv, Qishen [1 ]
Li, Xintian [2 ]
He, Shukai [2 ]
Zeng, Xiaozhe [2 ]
Yue, Yunqi [2 ]
机构
[1] Shenzhen Power Supply Co Ltd, Shenzhen 518000, Peoples R China
[2] Henan Relat Co Ltd, Zhengzhou 450001, Peoples R China
来源
ADVANCED SENSOR SYSTEMS AND APPLICATIONS IX | 2019年 / 11191卷
关键词
Absorption spectrum; H2S and H2O detection; TDLAS; High voltage combination; Detection limit; Response time;
D O I
10.1117/12.2537651
中图分类号
TB3 [工程材料学];
学科分类号
0805 ; 080502 ;
摘要
H2S and moisture content are important indicators to evaluate the potential faults and insulation performance of H2S electrical appliances. Currently, there is no report on the simultaneous detection of H2S gas and moisture content. In order to realize the accurate detection of H2S gas and H2O at the same time, lorentz simulation analysis was performed on the absorption spectra of H2S gas and H2O molecules. The absorption was strongest near 2684nm, and there was no cross interference of SF6 other decomposition products. H2S and moisture content at different concentrations were measured by TDLAS technology in a customized CW-DFB laser with a central wavelength of 2.68 mu m combined with a small-volume Herriott long-range cell with multiple reflections. In order to verify the detection ability of selected spectral lines to H2S gas and H2O molecules at low concentration, trace H2S and H2O vapor with SF6 as background were detected by direct absorption technology and wavelength modulation technology respectively. In the second harmonic absorption, the minimum detection lower limit of H2S and H2O is 9.01x10(-6) and 4.54x10(-6), respectively. The maximum harmonic signal amplitude has a good linear correlation with concentration, and the linear fitting degree R-2 is 0.978 and 0.997, respectively. SF6 gas displacement experiments with different flow rates showed that the equilibrium time of H2S and moisture content at 708mL/min was 90s and 100s, respectively. The response time of H2S and H2O at the same concentration and injection velocity is 30s and 45s, respectively. Wavelength modulation technology can provide a reliable experimental basis for the simultaneous detection of trace H2S and H2O in high voltage combination electrical appliances.
引用
收藏
页数:11
相关论文
共 12 条
  • [1] Simultaneous atmospheric nitrous oxide, methane and water vapor detection with a single continuous wave quantum cascade laser
    Cao, Yingchun
    Sanchez, Nancy P.
    Jiang, Wenzhe
    Griffin, Robert J.
    Xie, Feng
    Hughes, Lawrence C.
    Zah, Chung-en
    Tittel, Frank K.
    [J]. OPTICS EXPRESS, 2015, 23 (03): : 2121 - 2132
  • [2] [戴伟伟 Dai Weiwei], 2018, [高压电器, High Voltage Apparatus], V54, P254
  • [3] Jagadeeshwari M, 2011, APPL OPTICS, V50, P112
  • [4] SF6过热产生H2S的激光光谱法快速分析
    刘翔
    李瑶
    马冬莉
    胡雪蛟
    [J]. 武汉大学学报(工学版), 2018, 51 (08) : 740 - 744
  • [5] Measurement of Low-Concentration Water Vapor Based on Off-Axis Integrated Cavity Absorption Spectroscopy
    Yang Huinan
    Chen Ning
    Chen Jun
    [J]. ACTA OPTICA SINICA, 2018, 38 (02)
  • [6] A XML based information integration for field layer, MES and ERP
    Yang, Yimei
    Yin, Chao
    Li, Xiaobin
    [J]. 2017 5TH INTERNATIONAL CONFERENCE ON ENTERPRISE SYSTEMS (ES), 2017, : 46 - 51
  • [7] Yu Zhixiang, 2014, High Voltage Apparatus, V50, P42
  • [8] Synthesis of Two Well-Defined Quadruple-Stranded Copolymers having Two Kinds of Backbones by Postpolymerization of a Helical Template Polymer
    Zang, Yu
    Aoki, Toshiki
    Tanagi, Hiroyoki
    Matsui, Kana
    Teraguchi, Masahiro
    Kaneko, Takashi
    Ma, Liqun
    Jia, Hongge
    Shinohara, Ken-ichi
    [J]. MACROMOLECULAR RAPID COMMUNICATIONS, 2018, 39 (04)
  • [9] Zhang G. J, 2018, LASER JOURAL, V39, P15
  • [10] The Research for Trace Ammonia Escape Monitoring System Based on Tunable Diode Laser Absorption Spectroscopy
    Zhang Li-fang
    Wang Fei
    Yu Li-bin
    Yan Jian-hua
    Cen Ke-fa
    [J]. SPECTROSCOPY AND SPECTRAL ANALYSIS, 2015, 35 (06) : 1639 - 1642