Numerical simulation on synergetic optimization of non-equidistant fillings and non-uniform water distribution for wet cooling towers

被引:21
作者
Zhang, Deying [1 ]
Zhang, Zhengqing [1 ]
Han, Qiang [2 ]
Wu, Feixiang [2 ]
He, Suoying [1 ]
Gao, Ming [1 ]
机构
[1] Shandong Univ, Sch Energy & Power Engn, Shandong Engn Lab High Efficiency Energy Conserva, Jinan 250061, Shandong, Peoples R China
[2] Shandong Elect Power Engn Consulting Inst Corp LT, Jinan 250013, Shandong, Peoples R China
关键词
Natural draft wet cooling tower; Non-equidistant fillings; Non-uniform water distribution; Cooling performance; Synergetic optimization; THERMAL PERFORMANCE; PATTERNS; CROSS; FLOW;
D O I
10.1016/j.ijheatmasstransfer.2021.121676
中图分类号
O414.1 [热力学];
学科分类号
摘要
To improve the heat and mass transfer performance of large wet cooling towers, a synergetic optimiza-tion method of non-equidistant fillings and non-uniform water distribution was proposed in this paper. The impact of the optimization scheme on the cooling performance was studied for the cooling tower equipped for a 600 MW unit. Firstly, the fillings were divided into two zones, and the optimized inner fillings radius was obtained according to the different non-equidistant fillings patterns, namely the opti-mized radius dividing point in the filings zone. Then, the cooling performance variation under different non-uniform water distribution patterns was discussed based on this optimized radius dividing point. The simulation results showed that the synergetic optimization coupling the fillings and water-spraying zones improves significantly the uniformity of the air dynamic and temperature field. The water temperature drops and ventilation rate all increase firstly and then decrease with the increase of the water distri-bution ratio in the inner zone. Compared with the equidistant fillings layouts of 26 mm and 30 mm, after the synergetic optimization, the outlet water temperature drops increase by 0.21 degrees C, 0.22 degrees C, and the ventilation rate enhances by 6.68%, 1.13% respectively in the design condition, but 0.28 degrees C, 0.31 degrees C and 7.03%, 1.53% in the typical operating condition in summer. Additionally, the evaporation loss all decreases by about 3.3% in the design condition by comparison with the equidistant fillings layouts of 26 mm and 30 mm, but increases in the typical operating condition in summer. (c) 2021 Elsevier Ltd. All rights reserved.
引用
收藏
页数:9
相关论文
共 30 条
  • [1] CFD simulation of wet cooling towers
    Al-Waked, R
    Behnia, M
    [J]. APPLIED THERMAL ENGINEERING, 2006, 26 (04) : 382 - 395
  • [2] Enhancing performance of wet cooling towers
    Al-Waked, Rafat
    Behnia, Masud
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2007, 48 (10) : 2638 - 2648
  • [3] Crosswinds effect on the performance of natural draft wet cooling towers
    Al-Waked, Rafat
    [J]. INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2010, 49 (01) : 218 - 224
  • [4] Novel method for improving the cooling performance of natural draft wet cooling towers
    Chen, Xuehong
    Sun, Fengzhong
    Chen, Youliang
    Gao, Ming
    [J]. APPLIED THERMAL ENGINEERING, 2019, 147 : 562 - 570
  • [5] Experimental research of the cross walls effect on the thermal performance of wet cooling towers under crosswind conditions
    Chen, Youliang
    Sun, Fengzhong
    Wang, Hongguo
    Mu, Nasi
    Gao, Ming
    [J]. APPLIED THERMAL ENGINEERING, 2011, 31 (17-18) : 4007 - 4013
  • [6] Numerical simulation of thermal performance for super large-scale wet cooling tower equipped with an axial fan
    Dang, Zhigang
    Zhang, Zhengqing
    Gao, Ming
    He, Suoying
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2019, 135 : 220 - 234
  • [7] Dynamic modelling and operational optimisation of natural draft cooling towers
    Dhorat, A.
    Al-Obaidi, M. A.
    Mujtaba, I. M.
    [J]. THERMAL SCIENCE AND ENGINEERING PROGRESS, 2019, 9 : 30 - 43
  • [8] Performance characteristics of a trickle fill in cross- and counter-flow configuration in a wet-cooling tower
    Grobbelaar, P. J.
    Reuter, H. C. R.
    Bertrand, T. P.
    [J]. APPLIED THERMAL ENGINEERING, 2013, 50 (01) : 475 - 484
  • [9] Han D., 2017, TURBINE TECHNOL, V59, P253
  • [10] Loss coefficient correlation for wet-cooling tower fills
    Kloppers, JC
    Kröger, DG
    [J]. APPLIED THERMAL ENGINEERING, 2003, 23 (17) : 2201 - 2211