Energy-saving potential of separated two-phase thermosiphon loops for data center cooling

被引:9
作者
Sulaiman, Mohammed W. [1 ]
Daraghmeh, Hafiz M. [1 ,2 ]
Wang, Chi-Chuan [1 ]
机构
[1] Natl Chiao Tung Univ, Dept Mech Engn, Hsinchu 300, Taiwan
[2] Palestine Tech Univ, Dept Mech Engn, Tulkarm, Palestine
关键词
Data center; Free cooling; Energy-saving; Variable heating loads; Thermosiphon; Separated loop; HEAT-TRANSFER CHARACTERISTICS; CLOSED THERMOSIPHON; SYSTEM; RATIO;
D O I
10.1007/s10973-020-09499-w
中图分类号
O414.1 [热力学];
学科分类号
摘要
This study aims to experimentally examine the energy-saving potential by using R-134a filled separated two-phase thermosiphon loop (STPTL) for data center applications. A parametric study had been made to compare the energy consumption of two data center racks. Two fin-and-tube heat exchangers were attached to one of the racks to form two individual thermosiphon loops. The experiments were carried out subject to different operating conditions, including three ambient temperatures (20 degrees C, 23 degrees C, and 27 degrees C) and filling ratios ranging from 30 to 90% in association with heating loads ranging between 1.5 kW and 6 kW. Parametric influences regarding concentrated heat loading or uniform heat loading are studied. It was found that an appreciable energy-savings can be obtained at high filling ratios and a maximum of 49% energy-saving with the assistance of thermosiphon is observed. Accordingly, the rising of system pressure will result in noticeable savings. Relative to the uniform heat loading of the data rack, the thermosiphon shows even more energy-saving potential in concentrated heat loading. This phenomenon is more pronounced at a lower ambient temperature like 20 degrees C. On the other hand, there is no appreciable energy-saving for the thermosiphon between concentrated and uniform heating loads when the ambient temperature is high (27 degrees C). Furthermore, the influence of airflow rate was also investigated under various ambient temperatures with a 90% filling ratio and a heating load of 6 kW. The results revealed that the lower airflow rate in the thermosiphon yields comparatively better energy-saving than the higher flow rate. The study on the influence of using two STPTLs indicated that 15-23% energy-saving can be achieved at a 90% filling ratio and 6 kW heating load for all the studied ambient conditions if compared with testing each loop separately. Lower thermal resistance is seen at the higher filling ratios, ambient temperatures, and heating loads.
引用
收藏
页码:245 / 265
页数:21
相关论文
共 30 条
  • [1] Beitelmal M H., 2002, Two-Phase Loop: Compact Thermosyphon
  • [2] Sub-atmospheric boiling heat transfer and thermal performance of two-phase loop thermosyphon
    Chang, S. W.
    Lo, D. C.
    Chiang, K. F.
    Lin, C. Y.
    [J]. EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2012, 39 : 134 - 147
  • [3] Experimental investigations and modeling of a loop thermosyphon for cooling with zero electrical consumption
    Chehade, Ali
    Louahlia-Gualous, Hasna
    Le Masson, Stephane
    Lepinasse, Eric
    [J]. APPLIED THERMAL ENGINEERING, 2015, 87 : 559 - 573
  • [4] Investigation of Separated Two-Phase Thermosiphon Loop for Relieving the Air-Conditioning Loading in Datacenter
    Daraghmeh, Hafiz M.
    Sulaiman, Mohammed W.
    Yang, Kai-Shing
    Wang, Chi-Chuan
    [J]. ENERGIES, 2019, 12 (01):
  • [5] A review of current status of free cooling in datacenters
    Daraghmeh, Hafiz M.
    Wang, Chi-Chuan
    [J]. APPLIED THERMAL ENGINEERING, 2017, 114 : 1224 - 1239
  • [6] Experiment research on influence factors of the separated heat pipe system, especially the filling ratio and Freon types
    Ding, Tao
    Cao, Han Wen
    He, Zhi Guang
    Li, Zhen
    [J]. APPLIED THERMAL ENGINEERING, 2017, 118 : 357 - 364
  • [7] Fadhl B., 2015, Modelling of the Thermal Behaviour of a Two-Phase Closed Thermosyphon, P184
  • [8] Faghri A., 2017, HDB THERMAL SCI ENG, P2163
  • [9] Experimental analysis of Closed Loop Two Phase Thermosyphon (CLTPT) for energy systems
    Franco, Alessandro
    Filippeschi, Sauro
    [J]. EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2013, 51 : 302 - 311
  • [10] Closed Loop Two-Phase Thermosyphon of Small Dimensions: a Review of the Experimental Results
    Franco, Alessandro
    Filippeschi, Sauro
    [J]. MICROGRAVITY SCIENCE AND TECHNOLOGY, 2012, 24 (03) : 165 - 179