Numeral analysis model for shielding failure of transmission line under lightning stroke

被引:82
|
作者
He, JL [1 ]
Tu, YP
Zeng, R
Lee, JB
Chang, SH
Guan, ZC
机构
[1] Tsinghua Univ, Dept Elect Engn, Beijing 100084, Peoples R China
[2] N China Elect Power Univ Beijing, Dept Elect Engn, Beijing 102206, Peoples R China
[3] Korea Electrotechnol Res Inst, Elect Environm & Transmiss Grp, Chang Won 641600, South Korea
关键词
critical breakdown electrical field; electrical field; electrogeometric model; lightning leader; numerical analysis model; shielding failure; transmission line;
D O I
10.1109/TPWRD.2004.839189
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The shielding failure is the occurrence of a lightning stroke that bypasses the overhead ground wires and terminates on the phase conductors. The correct design to improve the shielding effect of transmission line to lightning is one of the key problems of transmission line design. A numerical analysis model for shielding failure of transmission line based on electromagnetic field theory is proposed in this paper. The electrical field of the system including lightning leader, transmission line and ground is solved, the range of lightning current striking the phase conductor is obtained, and the shielding failure probability of transmission line is calculated. The lightning leader model and the critical breakdown electrical field intensity of long gap are discussed. The analyzed results by numerical analysis model are compared with those by the electro-geometric model.
引用
收藏
页码:815 / 822
页数:8
相关论文
共 50 条
  • [41] Lightning return-stroke transmission line model based on CN Tower lightning data and derivative of Heidler function
    Milewski, M.
    Hussein, A. M.
    2008 CANADIAN CONFERENCE ON ELECTRICAL AND COMPUTER ENGINEERING, VOLS 1-4, 2008, : 1779 - 1784
  • [42] A Lightning Stroke Identification Method for HVDC Transmission Line Protection
    Liu, Zhen
    Gao, Houlei
    Li, Lin
    Peng, Fang
    2023 IEEE BELGRADE POWERTECH, 2023,
  • [43] Simulation of a lightning stroke into transmission line by Monte Carlo method
    Skok, S
    Uglesic, I
    Milardic, V
    IECON '98 - PROCEEDINGS OF THE 24TH ANNUAL CONFERENCE OF THE IEEE INDUSTRIAL ELECTRONICS SOCIETY, VOLS 1-4, 1998, : 2555 - 2557
  • [44] Discharge characteristics of 5 m long air gap under foggy conditions with lightning shielding of transmission line
    Taniguchi, Sakae
    Okabe, Shigemitsu
    Takahashi, Takeshi
    Shindo, Takatoshi
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2008, 15 (04) : 1031 - 1037
  • [45] An engineering model for transient analysis of grounding system under lightning strikes: Nonuniform transmission-line approach
    Liu, YQ
    Theethayi, N
    Thottappillil, R
    IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (02) : 722 - 730
  • [46] Experimental Research on Lightning Shielding Performance of Large Scaled UHV Transmission Line
    An, Yunzhu
    Wen, Xishan
    Lan, Lei
    Wang, Yu
    E, Shenglong
    Zhang, Jingzhuo
    Chen, Weijiang
    Dai, Min
    Li, Zhijun
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2015, 22 (05) : 2871 - 2878
  • [47] Application of GRNN to study of the lightning shielding performance for 500 kV transmission line
    School of Electrical Engineering, Wuhan University, Wuhan 430072, China
    Gaodianya Jishu, 2006, 5 (26-30):
  • [48] Study on the lightning protection of shielding failure for 1000 kV UHV transmission lines
    Wuhan High Voltage Research Institute of SGCC, Wuhan 430074, China
    Gaodianya Jishu, 2006, 12 (52-54):
  • [49] Lightning Attachment Models and Maximum Shielding Failure Current: Application to Transmission Lines
    Mikropoulos, Pantelis N.
    Tsovilis, Thomas E.
    2009 IEEE BUCHAREST POWERTECH, VOLS 1-5, 2009, : 1867 - 1874
  • [50] Classification of lightning stroke on transmission line using multi-resolution analysis and machine learning
    Morales, J. A.
    Orduna, E.
    Rehtanz, C.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2014, 58 : 19 - 31