A novel operation approach for the energy efficiency improvement of the HVAC system in office spaces through real-time big data analytics

被引:44
作者
Li, Wenzhuo [1 ]
Koo, Choongwan [2 ]
Hong, Taehoon [3 ]
Oh, Jeongyoon [2 ]
Cha, Seung Hyun [4 ]
Wang, Shengwei [1 ]
机构
[1] Hong Kong Polytech Univ, Hung Hom, Dept Bldg Serv Engn, Kowloon, Hong Kong, Peoples R China
[2] Incheon Natl Univ, Div Architecture & Urban Design, Incheon, South Korea
[3] Yonsei Univ, Dept Architecture & Architectural Engn, Seoul 03722, South Korea
[4] Hanyang Univ, Dept Interior Architecture Design, Seoul 04763, South Korea
基金
新加坡国家研究基金会;
关键词
Real-time big data analytics; Energy efficiency; Set-point temperature; Change point analysis; Occupancy-based control; CO2; concentration; OCCUPANCY DETECTION; FAULT-DETECTION; INDOOR AIR; ELECTRICITY CONSUMPTION; PREDICTIVE CONTROL; THERMAL COMFORT; BUILDINGS; TEMPERATURE; PERFORMANCE; ALGORITHM;
D O I
10.1016/j.rser.2020.109885
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Since a traditional centralized control system (e.g., building energy management system) with a fixed schedule and manual control is not appropriate to irregularly occupied rooms, it is expected to have a large amount of energy saving potential in operating the HVAC system. To overcome this challenge, this study aimed to develop a novel operation approach for the energy efficiency improvement of the HVAC system in office spaces. The real-time indoor environmental indicators were collected and analyzed to evaluate the current operation status of the HVAC system as well as to propose a novel control strategy in two ways. The significant findings can be illustrated as follows. First, it could be stated that occupants would tend to establish a lower set-point temperature for a cooler indoor environment. To solve this issue, a basic control strategy was proposed to detect the anomaly detection of the HVAC system and to automatically adjust the indoor temperature within a preferred range. Second, it could be evaluated that the HVAC system would be kept operating since occupants would forget to turn off the HVAC system after the meetings. To solve this issue, an advanced control strategy was proposed to operate the automatic on/off control of the HVAC system by considering the indoor temperature and CO2 concentration in real time. The proposed strategies can contribute to a large amount of energy savings in operating the HVAC system of irregularly occupied spaces.
引用
收藏
页数:15
相关论文
共 65 条
  • [21] Distributed air conditioning control in commercial buildings based on a physical-statistical approach
    Ghofrani, Ali
    Jafari, Mohsen A.
    [J]. ENERGY AND BUILDINGS, 2017, 148 : 106 - 118
  • [22] Understanding the energy consumption and occupancy of a multi-purpose academic building
    Gul, Mehreen S.
    Patidar, Sandhya
    [J]. ENERGY AND BUILDINGS, 2015, 87 : 155 - 165
  • [23] Formaldehyde concentration and its influencing factors in residential homes after decoration at Hangzhou, China
    Guo, Min
    Pei, Xiaoqiang
    Mo, Feifei
    Liu, Jianlei
    Shen, Xueyou
    [J]. JOURNAL OF ENVIRONMENTAL SCIENCES, 2013, 25 (05) : 908 - 915
  • [24] Guralnik V., 1999, SIGKDD, P33
  • [25] A review on sustainable construction management strategies for monitoring, diagnosing, and retrofitting the building's dynamic energy performance: Focused on the operation and maintenance phase
    Hong, Taehoon
    Koo, Choongwan
    Kim, Jimin
    Lee, Minhyun
    Jeong, Kwangbok
    [J]. APPLIED ENERGY, 2015, 155 : 671 - 707
  • [26] Evaluation of a real-time method for monitoring volatile organic compounds in indoor air in a Japanese university
    Hori, Hajime
    Ishimatsu, Sumiyo
    Fueta, Yukiko
    Ishidao, Toru
    [J]. ENVIRONMENTAL HEALTH AND PREVENTIVE MEDICINE, 2013, 18 (04) : 285 - 292
  • [27] A statistically-based fault detection approach for environmental and energy management in buildings
    Horrigan, Matthew
    Turner, William J. N.
    O'Donnell, James
    [J]. ENERGY AND BUILDINGS, 2018, 158 : 1499 - 1509
  • [28] Extending air temperature setpoints: Simulated energy savings and design considerations for new and retrofit buildings
    Hoyt, Tyler
    Arens, Edward
    Zhang, Hui
    [J]. BUILDING AND ENVIRONMENT, 2015, 88 : 89 - 96
  • [29] Indoor air quality varies with ventilation types and working areas in hospitals
    Jung, Chien-Cheng
    Wu, Pei-Chih
    Tseng, Chao-Heng
    Su, Huey-Jen
    [J]. BUILDING AND ENVIRONMENT, 2015, 85 : 190 - 195
  • [30] Katipamula S., 2012, Small and medium sized commercial building monitoring and controls needs: a scoping study