Evaluating Indoor Carbon Dioxide Concentration and Ventilation Rate of Research Student Offices in Chinese Universities: A Case Study

被引:4
作者
Fan, Guangtao [1 ]
Chang, Haoran [1 ]
Sang, Chenkai [1 ]
Chen, Yibo [1 ]
Ning, Baisong [1 ]
Liu, Changhai [1 ]
机构
[1] Zhengzhou Univ, Sch Civil Engn, Zhengzhou 450001, Peoples R China
基金
中国国家自然科学基金; 中国博士后科学基金;
关键词
indoor air quality; high occupancy rate; natural ventilation; university building; AIR-QUALITY;
D O I
10.3390/pr10081434
中图分类号
TQ [化学工业];
学科分类号
0817 ;
摘要
This work provides a case study on the indoor environment and ventilation rate of naturally ventilated research student rooms in Chinese universities. In the measured room, air temperature, relative humidity and carbon dioxide (CO2) concentration were monitored during the heating period for 4 weeks. The number of indoor occupants, occupied time of the room and window/door-opening cases were simultaneously recorded. Results showed the research student room was occupied for an average of 12.0 h each day. Due to a large indoor and outdoor temperature difference during the heating season, and occupants' adaption to indoor environment, indoor occupants seldom open windows/doors for ventilation. Air exchange of the room only by air infiltration cannot meet the ventilation requirement. As a result, an average of 77.6% of measured CO2 data each day exceeded 1000 ppm during occupied time. In fact, according to CO2 data, it was observed that window/door opening could effectively decrease indoor CO(2 )concentration. Therefore, intermittent window/door opening or CO2-based demand-controlled ventilation facilities were suggested for improving indoor air quality of such rooms. Additionally, special attention should be paid to other possible outdoor pollution.
引用
收藏
页数:16
相关论文
共 23 条
  • [1] [Anonymous], 2013, 621 ANSIASHRAE
  • [2] [Anonymous], 2012, D6245 ASTM
  • [3] [Anonymous], 2002, 18883 GBT MIN ENV PR
  • [4] [Anonymous], 2018, BUILD AR IND REG I H
  • [5] [Anonymous], CHINAS STAT YB 2021
  • [6] [Anonymous], 2013, ASHRAE Handbook: Fundamentals
  • [7] Statistical Evaluation of Indoor Air Quality Parameters in Classrooms of a University
    Argunhan, Zeki
    Avci, Ali Serkan
    [J]. ADVANCES IN METEOROLOGY, 2018, 2018
  • [8] Indoor temperature, relative humidity and CO2 levels assessment in academic buildings with different heating, ventilation and air-conditioning systems
    Asif, Ayesha
    Zeeshan, Muhammad
    Jahanzaib, Muhammad
    [J]. BUILDING AND ENVIRONMENT, 2018, 133 : 83 - 90
  • [9] Chang FH, 2009, INT J ENVIRON RES, V3, P517
  • [10] Indoor air quality in university environments
    Di Giulio, Mara
    Grande, Rossella
    Di Campli, Emanuela
    Di Bartolomeo, Soraya
    Cellini, Luigina
    [J]. ENVIRONMENTAL MONITORING AND ASSESSMENT, 2010, 170 (1-4) : 509 - 517