Cascade deep air dehumidification with integrated direct-contact cooling and liquid desiccant absorption

被引:22
作者
Fang, Song
Xu, Zhuoren
Zhou, Xia
Zhang, Hanwei
Zhi, Xiaoqin
Qiu, Limin
Wang, Kai [1 ]
机构
[1] Zhejiang Univ, Inst Refrigerat & Cryogen, Hangzhou 310027, Peoples R China
基金
中国国家自然科学基金;
关键词
Liquiddesiccant; Deepairdehumidification; Direct-contactcooling; Multi-stage; Internally-cooled; Coolingallocation; EXPERIMENTAL PERFORMANCE; EXERGY ANALYSIS; MASS-TRANSFER; SYSTEM; MODEL;
D O I
10.1016/j.enconman.2022.115959
中图分类号
O414.1 [热力学];
学科分类号
摘要
Deep dehumidification of the feed air is expected for the energy saving and stable operation of the air compression process in large-scale industries. Liquid desiccant-based dehumidification technology provides an alternative solution mainly featuring the continuous operation and low regeneration temperature, but the conventional systems still face a challenge to achieve the deep air dehumidification at high air-to-solution flow ratios, especially under high humidity conditions. Based on the cascade matching of driving forces, this study first presents a cascade deep air dehumidification system integrating a direct-contact cooling module (DCCD) and multi-stage internally-cooled liquid desiccant module (MILDD). In particular, the DCCD uses a novel internal matrix structure where the moist air is in direct contact with the cooling water with low hygroscopic. To evaluate the proposed system, a complete thermodynamic model is developed based on the newly-fitted general empirical correlation for mass transfer coefficient between the moist air and cooling water. The numerical model is validated against the initial experiment of the DCCD-MILDD test bench with a mean relative discrepancy of 6%-9%. The supplied air states and energy performance of the cascade system are evaluated at low humidity and high humidity conditions. The cooling water utilization is further improved by two series-looping schemes of cooling water allocation. Numerical results show that the DCCD-MILDD cascade system can achieve deep air dehumidification with the outlet air humidity ratio lower than 6.2 g/kg and the air-to-solution flow ratios over 4.0 even at high humidity conditions. This attributes to an improvement of the coefficient of performance and exergy efficiency, respectively 1.90 and 0.57. This work may provide an effective design of the liquid desiccant-based deep air dehumidification systems applied to the large-scale air compression process.
引用
收藏
页数:15
相关论文
共 38 条
[11]   High-performance multi-stage internally-cooled liquid desiccant dehumidifier for high gas-liquid flow ratios [J].
Fang, Song ;
Xu, Zhuoren ;
Zhang, Hanwei ;
Rong, Yangyiming ;
Zhou, Xia ;
Zhi, Xiaoqin ;
Wang, Kai ;
Markides, Christos N. ;
Qiu, Limin .
ENERGY CONVERSION AND MANAGEMENT, 2021, 250
[12]   Multi-stage internally-cooled membrane-based liquid desiccant dehumidifiers: Driving-force based insights into structural improvement [J].
Fang, Song ;
Zhou, Xia ;
Rong, Yangyiming ;
Zhi, Xiaoqin ;
Wang, Kai ;
Qiu, Limin .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2021, 171
[13]   On-site performance investigation of a desiccant wheel deep- dehumidification system applied in lithium battery manufacturing plant [J].
Guan, Bowen ;
Zhang, Tao ;
Liu, Xiaohua .
ENERGY AND BUILDINGS, 2021, 232
[14]   Exergy analysis and performance improvement of liquid-desiccant deep-dehumidification system: An engineering case study [J].
Guan, Bowen ;
Zhang, Tao ;
Jun, Liu ;
Liu, Xiaohua .
ENERGY, 2020, 196
[15]   Experimental and numerical investigation of a novel hybrid deep-dehumidification system using liquid desiccant [J].
Guan, Bowen ;
Liu, Xiaohua ;
Zhang, Tao ;
Ma, Zhiyao ;
Chen, Liangliang ;
Chen, Xiaoyang .
ENERGY CONVERSION AND MANAGEMENT, 2019, 192 :396-411
[16]   Next-generation HVAC: Prospects for and limitations of desiccant and membrane-based dehumidification and cooling [J].
Labban, Omar ;
Chen, Tianyi ;
Ghoniem, Ahmed F. ;
Lienhard, John H., V ;
Norford, Leslie K. .
APPLIED ENERGY, 2017, 200 :330-346
[17]   Performance comparison and exergy analysis of different flow types in internally-cooled liquid desiccant dehumidifiers (ICDs) [J].
Liu, Jun ;
Liu, Xiaohua ;
Zhang, Tao .
APPLIED THERMAL ENGINEERING, 2018, 142 :278-291
[18]   Heat and mass transfer model of cross flow liquid desiccant air dehumidifier/regenerator [J].
Liu, X. H. ;
Jiang, Y. ;
Qu, K. Y. .
ENERGY CONVERSION AND MANAGEMENT, 2007, 48 (02) :546-554
[19]   Performance analysis on the internally cooled dehumidifier using liquid desiccant [J].
Liu, X. H. ;
Chang, X. M. ;
Xia, J. J. ;
Jiang, Y. .
BUILDING AND ENVIRONMENT, 2009, 44 (02) :299-308
[20]   Experimental and theoretical research of a fin-tube type internally-cooled liquid desiccant dehumidifier [J].
Luo, Yimo ;
Shao, Shuangquan ;
Xu, Hongbo ;
Tian, Chongqing ;
Yang, Hongxing .
APPLIED ENERGY, 2014, 133 :127-134