Numerical simulation on the heat transfer characteristics of two-phase loop thermosyphon with high filling ratios

被引:24
作者
Wang, Kuiming [1 ]
Hu, Chengzhi [1 ]
Jiang, Bo [1 ]
Hu, Xianfeng [1 ]
Tang, Dawei [1 ]
机构
[1] Dalian Univ Technol, Sch Energy & Power Engn, Key Lab Ocean Energy Utilizat & Energy Conservat, Minist Educ, Dalian 116024, Peoples R China
基金
中国国家自然科学基金;
关键词
Two-phase loop thermosiphon; High filling ratio; Heat transfer; CFD; EVAPORATOR; SYSTEM; INSTABILITY;
D O I
10.1016/j.ijheatmasstransfer.2021.122311
中图分类号
O414.1 [热力学];
学科分类号
摘要
A B S T R A C T The two-phase loop thermosyphon (TPLT) with a high filling ratio is considered an efficient heat transfer device and therefore has a good application prospect in the field of high heat flux dissipation engineering. However, the heat transfer mechanism of the TPLT with high filling ratios remains elusive. In this study, we establish a computational fluid dynamics (CFD) model of the loop thermosyphon. In order to accurately simulate boiling and condensation processes, we take into account the relationship between saturation temperature and pressure in the phase change model. There were two flow patterns, i.e., the bubbly flow and the slug flow, under low filling ratios in the heating section, in which the pool boiling dominates the main heat transfer mechanism, and dropwise condensation occurred in the condensation section. The driving force to propel the liquid during the vapor bubbles rise cannot be transferred to the liquid in the right tube, resulting in lower flow velocity. In stark contrast, the single-phase flow and the bubbly flow occurred periodically in the loop thermosyphon with high filling ratios, in which the dominant heat transfer mechanism is the flow boiling. The rising bubbles promote the clockwise flow of liquid in the loop like a pump. Because of the switch of the heat transfer mechanism, the average flow velocity increased, and the thermal resistance decreased. The minimum thermal resistance was 0.15 K/W under a filling ratio of 75%, and the maximum average velocity of the fluid was 0.19 m/s. Furthermore, we found a strong coupling relationship between the heat transfer performance and the flow characteristics of the loop thermosyphon. For low filling ratios, local dry-out occurred in the loop thermosyphon under a high input heat flux, leading to an increase in the thermal resistance. For high filling ratios, the average velocity of the fluid was augmented with the increase in heating power, while the liquid was capable of being replenished quickly in the heating section to avoid the dry-out. Therefore, the loop thermosyphon with high filling ratios enables a better heat transfer performance under a high heat flux than those with low filling ratios. (c) 2021 Elsevier Ltd. All rights reserved.
引用
收藏
页数:15
相关论文
共 30 条
[21]   Heat transfer and instability characteristics of a loop thermosyphon with wide range of filling ratios [J].
Liu, Yun ;
Li, Zhigang ;
Li, Yuhua ;
Jiang, Yuyan ;
Tang, Dawei .
APPLIED THERMAL ENGINEERING, 2019, 151 :262-271
[22]   Loop thermosiphon thermal collector for waste heat recovery power generation [J].
Matsubara, Koji ;
Nakakura, Mitsuho ;
Bellan, Selvan ;
Maezawa, Kazuo .
EXPERIMENTAL HEAT TRANSFER, 2019, 32 (03) :201-218
[23]   Thermal resistance of a thermosyphon filled with R410A operating at low evaporator temperature [J].
Ong, K. S. ;
Goh, Gabriel ;
Tshai, K. H. ;
Chin, W. M. .
APPLIED THERMAL ENGINEERING, 2016, 106 :1345-1351
[24]   Size effects of a portable two-phase electronics cooling loop [J].
Saenen, Tom ;
Baelmans, Martine .
APPLIED THERMAL ENGINEERING, 2013, 50 (01) :1174-1185
[25]   Two-phase thermosyphon loop for cooling outdoor telecommunication equipments [J].
Samba, Ahmadou ;
Louahlia-Gualous, Hasna ;
Le Masson, Stephane ;
Noerterhaeuser, David .
APPLIED THERMAL ENGINEERING, 2013, 50 (01) :1351-1360
[26]   Analysis on energy efficiency of an integrated heat pipe system in data centers [J].
Wang, Zhenying ;
Zhang, Xiaotong ;
Li, Zhen ;
Luo, Ming .
APPLIED THERMAL ENGINEERING, 2015, 90 :937-944
[27]   INFLUENCE OF VAPOR BUBBLES ON THE THERMAL PERFORMANCE OF A TWO-PHASE CLOSED THERMOSYPHON LOOP WITH A LIQUID HEAT TRANSFER AGENT [J].
Wei, Lingjiao ;
Yuan, Dazhong ;
Guo, Chaohong ;
Tang, Dawei .
HEAT TRANSFER RESEARCH, 2016, 47 (12) :1109-1120
[28]   Numerical simulation of wickless gravity-assisted two-phase cooling system used in heavy duty extrusion pelleting line [J].
Xia, Liangzhi ;
Dong, Dandan ;
Zhang, Hongchun ;
Yu, Caiyuan .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2017, 111 :540-550
[29]   Integrated system of mechanical refrigeration and thermosyphon for free cooling of data centers [J].
Zhang, Hainan ;
Shao, Shuangquan ;
Xu, Hongbo ;
Zou, Huiming ;
Tian, Changqing .
APPLIED THERMAL ENGINEERING, 2015, 75 :185-192
[30]   Effect of servers' arrangement on the performance of a loop thermosyphon system used in data center [J].
Zou, Sikai ;
Zhang, Quan ;
Yue, Chang ;
Du, Sheng .
APPLIED THERMAL ENGINEERING, 2021, 192