An Active Voltage Coordinate Control Strategy of DFIG-Based Wind Farm with Hybrid Energy Storage System

被引:4
作者
Song, Yuyan [1 ]
Wang, Yuhong [1 ]
Zeng, Qi [1 ]
Liao, Jianquan [1 ]
Zheng, Zongsheng [1 ]
Chen, Shiyu [1 ]
Liao, Yiben [1 ]
机构
[1] Sichuan Univ, Coll Elect Engn, Chengdu 610065, Peoples R China
关键词
active voltage coordinate control; hybrid energy storage system; voltage stability; wind speed variations; DFIG-based wind farm; REACTIVE POWER-CONTROL; GENERATION; ENHANCEMENT; STABILITY; SUPPORT;
D O I
10.3390/electronics10243060
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
In a power system with wind farms, the point of common coupling (PCC) usually suffers from voltage instability under large wind speed variations and the load impact. Using the internal converter of a doubly fed induction generator (DFIG)-based wind turbine to provide voltage support auxiliary service is an effective scheme to suppress the voltage fluctuation at PCC. To satisfy the reactive power demand of the connected grid, an active voltage coordinate control strategy with the hybrid energy storage system of the wind farm is proposed. The dynamic reactive power balance model is established to show the interaction between the reactive power limitation of the wind farm and the reactive power compensation demand of the grid. This indicates the initial conditions of the active voltage coordinate control strategy. According to the critical operating point and the operation state of the DFIG, the active and reactive power coordinate control strategy composed of active omega-beta coordinate control and active beta control is proposed to enhance the reactive power support capability and stabilize the grid voltage. To compensate the active power shortage, an auxiliary control strategy based on the hybrid energy storage system is introduced. The simulation results show that the proposed strategy can suppress the voltage fluctuation effectively and make full use of primary energy.
引用
收藏
页数:21
相关论文
共 38 条
[1]   Adaptive voltage control strategy for variable-speed wind turbine connected to a weak network [J].
Abulanwar, Sayed ;
Hu, Weihao ;
Chen, Zhe ;
Iov, Florin .
IET RENEWABLE POWER GENERATION, 2016, 10 (02) :238-249
[2]  
Alberta Electric Power System Operator, 2004, WIND POW FAC TECHN R
[3]  
[Anonymous], 2020, Global Wind Report 2019
[4]   A Consensus Approach to Real-Time Distributed Control of Energy Storage Systems in Wind Farms [J].
Baros, Stefanos ;
Ilic, Marija D. .
IEEE TRANSACTIONS ON SMART GRID, 2019, 10 (01) :613-625
[5]  
Berndt H., 2007, NETWORK SYSTEM RULES
[6]   Coordination of PSSs and SVC Damping Controller to Improve Probabilistic Small-Signal Stability of Power System With Wind Farm Integration [J].
Bian, X. Y. ;
Geng, Yan ;
Lo, Kwok L. ;
Fu, Yang ;
Zhou, Q. B. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2016, 31 (03) :2371-2382
[7]  
China Electric Power Research Institute, 2011, 15472011 SNT
[8]   Fuzzy-based approach for power smoothing of a full-converter wind turbine generator using a supercapacitor energy storage [J].
de Carvalho, Wilhiam C. ;
Bataglioli, Rodrigo P. ;
Fernandes, Ricardo A. S. ;
Coury, Denis, V .
ELECTRIC POWER SYSTEMS RESEARCH, 2020, 184
[9]   Coordination Strategy of Large-Scale DFIG-Based Wind Farm for Voltage Support With High Converter Capacity Utilization [J].
Dong, Zhen ;
Li, Zhongguo ;
Du, Lingyu ;
Liu, Yixing ;
Ding, Zhengtao .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2021, 12 (02) :1416-1425
[10]  
ELTRA Transmission System Planning, 2000, ELT1999411A, V2nd