Investigation on the thermal performance of a novel spray tower with upward spraying and downward gas flow

被引:30
作者
Cui, Haijiao [1 ]
Li, Nianping [1 ]
Peng, Jinqing [1 ]
Yin, Rongxin [1 ,2 ]
Li, Jingming [1 ]
Wu, Zhibin [1 ]
机构
[1] Hunan Univ, Coll Civil Engn, Changsha 410081, Hunan, Peoples R China
[2] Lawrence Berkeley Natl Lab, Energy Storage & Distributed Resources Div, Berkeley, CA USA
关键词
Direct-contact heat and mass transfer; Spray systems; Reversibly used cooling towers; Particulate removal; Heat pumps; SHOWER COOLING-TOWER; NUMERICAL-SIMULATION; CO2; ABSORPTION; WATER SPRAY; FLUE-GAS; LIQUID; AIR; ENERGY; TEMPERATURE; SYSTEM;
D O I
10.1016/j.apenergy.2018.09.123
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper presents the design and evaluation of a novel spray tower which called the reversibly used cooling tower with upward spraying and downward gas flow (RUCT-UD). Unlike conventional spray towers, RUCT-UD has no high-resistance drift eliminator and no restriction on the minimum droplet diameter, which gives it the potential to achieve better performance of heat and mass transfer and particle scavenging. A mathematical model was developed and validated by field experiments. This model is highly efficient in calculation due to the simultaneous consideration of rising and falling droplets. Using the model, the heat and mass transfer characteristics were investigated by, a parametric study, which provides a theoretical basis for the tower design. After that, the performance of RUCT-UD was compared with that of other spray-type RUCTs. Results show that RUCT-UD is 45% shorter than RUCT-UU (the reversibly used cooling tower with upward spraying and upward gas flow) and RUCT-DU (the reversibly used cooling tower with downward spraying and upward gas flow), meanwhile it could realize a high thermal performance like RUCT-UU. The particle collection efficiency of PM2.5 for RUCT-UD is 75.9%, which is higher than that of RUCT-UU (48.9%) and that of RUCT-DU (61.1%). The configuration of the proposed RUCT-UD might be applied to other spray towers for the performance improvement.
引用
收藏
页码:12 / 21
页数:10
相关论文
共 42 条
  • [11] Douglas J. F., 2011, FLUID MECH
  • [12] Flue gas desulphurization by spray dry absorption
    Hill, FF
    Zank, J
    [J]. CHEMICAL ENGINEERING AND PROCESSING-PROCESS INTENSIFICATION, 2000, 39 (01) : 45 - 52
  • [13] Huang S, 2017, INT J REFRIG, V77
  • [14] Incropera F.P., 2011, FUNDAMENTALS HEAT MA
  • [15] Performance control of a spray passive down-draft evaporative cooling system
    Kang, Daeho
    Strand, Richard K.
    [J]. APPLIED ENERGY, 2018, 222 : 915 - 931
  • [16] Significance of parameters affecting the performance of a passive down-draft evaporative cooling (PDEC) tower with a spray system
    Kang, Daeho
    Strand, Richard K.
    [J]. APPLIED ENERGY, 2016, 178 : 269 - 280
  • [17] Lian Z, 2001, PRINCIPLES EQUIPMENT
  • [18] Temperature profile in countercurrent/cocurrent spray towers
    Makkinejad, N
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2001, 44 (02) : 429 - 442
  • [19] Numerical analysis of seawater desalination based on a solar chimney power plant
    Ming, Tingzhen
    Gong, Tingrui
    de Richter, Renaud K.
    Cai, Cunjin
    Sherif, S. A.
    [J]. APPLIED ENERGY, 2017, 208 : 1258 - 1273
  • [20] Performance characteristics of the particulates scrubbing in a counter-current spray-column
    Mohan, B. Raj
    Biswas, Sanjay
    Meikap, B. C.
    [J]. SEPARATION AND PURIFICATION TECHNOLOGY, 2008, 61 (01) : 96 - 102