Investigation on the thermal performance of a novel spray tower with upward spraying and downward gas flow

被引:30
作者
Cui, Haijiao [1 ]
Li, Nianping [1 ]
Peng, Jinqing [1 ]
Yin, Rongxin [1 ,2 ]
Li, Jingming [1 ]
Wu, Zhibin [1 ]
机构
[1] Hunan Univ, Coll Civil Engn, Changsha 410081, Hunan, Peoples R China
[2] Lawrence Berkeley Natl Lab, Energy Storage & Distributed Resources Div, Berkeley, CA USA
关键词
Direct-contact heat and mass transfer; Spray systems; Reversibly used cooling towers; Particulate removal; Heat pumps; SHOWER COOLING-TOWER; NUMERICAL-SIMULATION; CO2; ABSORPTION; WATER SPRAY; FLUE-GAS; LIQUID; AIR; ENERGY; TEMPERATURE; SYSTEM;
D O I
10.1016/j.apenergy.2018.09.123
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper presents the design and evaluation of a novel spray tower which called the reversibly used cooling tower with upward spraying and downward gas flow (RUCT-UD). Unlike conventional spray towers, RUCT-UD has no high-resistance drift eliminator and no restriction on the minimum droplet diameter, which gives it the potential to achieve better performance of heat and mass transfer and particle scavenging. A mathematical model was developed and validated by field experiments. This model is highly efficient in calculation due to the simultaneous consideration of rising and falling droplets. Using the model, the heat and mass transfer characteristics were investigated by, a parametric study, which provides a theoretical basis for the tower design. After that, the performance of RUCT-UD was compared with that of other spray-type RUCTs. Results show that RUCT-UD is 45% shorter than RUCT-UU (the reversibly used cooling tower with upward spraying and upward gas flow) and RUCT-DU (the reversibly used cooling tower with downward spraying and upward gas flow), meanwhile it could realize a high thermal performance like RUCT-UU. The particle collection efficiency of PM2.5 for RUCT-UD is 75.9%, which is higher than that of RUCT-UU (48.9%) and that of RUCT-DU (61.1%). The configuration of the proposed RUCT-UD might be applied to other spray towers for the performance improvement.
引用
收藏
页码:12 / 21
页数:10
相关论文
共 42 条
  • [1] A one-dimensional plug-flow model of a counter-current spray drying tower
    Ali, Muzammil
    Mahmud, Tariq
    Heggs, Peter John
    Ghadiri, Mojtaba
    Djurdjevic, Dusan
    Ahmadian, Hossein
    de Juan, Luis Martin
    Amador, Carlos
    Bayly, Andrew
    [J]. CHEMICAL ENGINEERING RESEARCH & DESIGN, 2014, 92 (05) : 826 - 841
  • [2] ASHRAE, 2009, ASHRAE HDB FUND, P13
  • [3] Butcher JC., 1987, The numerical analysis of ordinary differential equations: Runge-Kutta and general linear methods
  • [4] Study of Heat-source-tower Heat Pump System Efficiency
    Cheng, Jianlin
    Li, Nianpin
    Wang, Kuan
    [J]. 9TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING (ISHVAC) JOINT WITH THE 3RD INTERNATIONAL CONFERENCE ON BUILDING ENERGY AND ENVIRONMENT (COBEE), 2015, 121 : 915 - 921
  • [5] Aerosol particles scavenging by a droplet: Microphysical modeling in the Greenfield gap
    Cherrier, Gael
    Belut, Emmanuel
    Gerardin, Fabien
    Taniere, Anne
    Rimbert, Nicolas
    [J]. ATMOSPHERIC ENVIRONMENT, 2017, 166 : 519 - 530
  • [6] Optimization of reversibly used cooling tower with downward spraying
    Cui, Haijiao
    Li, Nianping
    Wang, Xinlei
    Peng, Jinqing
    Li, Yuan
    Wu, Zhibin
    [J]. ENERGY, 2017, 127 : 30 - 43
  • [7] Modeling the particle scavenging and thermal efficiencies of a heat absorbing scrubber
    Cui, Haijiao
    Li, Nianping
    Peng, Jinqing
    Cheng, Jianlin
    Zhang, Nan
    Wu, Zhibin
    [J]. BUILDING AND ENVIRONMENT, 2017, 111 : 218 - 227
  • [8] Study on the dynamic and thermal performances of a reversibly used cooling tower with upward spraying
    Cui, Haijiao
    Li, Nianping
    Peng, Jinqing
    Cheng, Jianlin
    Li, Shengbing
    [J]. ENERGY, 2016, 96 : 268 - 277
  • [9] Synergistic capture of fine particles in wet flue gas through cooling and condensation
    Cui, Lin
    Song, Xiangda
    Li, Yuzhong
    Wang, Yang
    Feng, Yupeng
    Yan, Lifan
    Dong, Yong
    [J]. APPLIED ENERGY, 2018, 225 : 656 - 667
  • [10] New concept of spray saturation tower for micro Humid Air Turbine applications
    De Paepe, W.
    Contino, F.
    Delattin, F.
    Bram, S.
    De Ruyck, J.
    [J]. APPLIED ENERGY, 2014, 130 : 723 - 737