Novel Gas-Sensitive Material for Monitoring the Status of SF6 Gas-Insulated Switches: Gese Monolayer

被引:7
|
作者
Qian, Guochao [1 ,2 ]
Hu, Xiqian [1 ]
Chen, Weigen [1 ]
Zhou, Qu [3 ]
机构
[1] Chongqing Univ, State Key Lab Power Transmiss Equipment & Syst Se, Chongqing 400030, Peoples R China
[2] Yunnan Power Grid Co Ltd, Elect Power Sci Res Inst, Kunming 650200, Yunnan, Peoples R China
[3] Southwest Univ, Coll Engn & Technol, Chongqing 400715, Peoples R China
基金
中国国家自然科学基金;
关键词
DFT; GeSe monolayer; SF6 decomposition product; adsorption; gas sensors; PROMISING CANDIDATE; SENSING PROPERTIES; INN MONOLAYER; 1ST-PRINCIPLES; ADSORPTION; PRODUCTS; DETECT;
D O I
10.3390/chemosensors10070246
中图分类号
O65 [分析化学];
学科分类号
070302 ; 081704 ;
摘要
Detecting the decomposition components of SF6 insulating gas is recognized as an effective means to monitor the operating status of the SF6 insulating switch. In this paper, the adsorption characteristics of a new two-dimensional material GeSe for five SF6 decomposition gases (SO2, SOF2, SO2F2, H2S and HF) are reported by first-principles simulation. Through the analysis of the change of energy band structure, density of states distribution, and gas desorption time, it is found that GeSe has the potential as a gas-sensitive material for the selective detection of SO2F2, and the computational work in this paper provides theoretical guidance for the development of new gas-sensitive sensors applied in monitoring SF6 insulated switches.
引用
收藏
页数:11
相关论文
共 50 条
  • [1] Monitoring of SF6 gas admixtures in gas-insulated electrical equipment
    Paul, Th. A.
    Kramer, A.
    PROCEEDINGS OF 2012 IEEE INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (IEEE CMD 2012), 2012, : 493 - 496
  • [2] SF6 DECOMPOSITION IN GAS-INSULATED EQUIPMENT
    CHU, FY
    IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1986, 21 (05): : 693 - 725
  • [3] SF6 GAS-INSULATED SWITCHGEAR FOR ALL APPLICATIONS
    SZENTEVARGA, HP
    TECCHIO, P
    BROWN BOVERI REVIEW, 1983, 70 (1-2): : 81 - 86
  • [4] SF6 concentration sensor for gas-insulated electrical switchgear
    Paul, Th. A.
    Porus, M.
    Galletti, B.
    Kramer, A.
    SENSORS AND ACTUATORS A-PHYSICAL, 2014, 206 : 51 - 56
  • [5] Gas-insulated switchgear state monitoring based on SF6 decomposition products detection
    Yan, Xianglian
    Song, Gao
    Wang, Chengyu
    Ji, Yansong
    Yang, Ren
    Jian, Yongfeng
    Liu, Hanmei
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2014, 34 (06): : 83 - 88
  • [6] SF6 GAS INSULATED LOAD INTERRUPTING SWITCHES WITH FUSING
    SCHAFFER, JS
    PATEL, JR
    RUETH, WR
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1984, 103 (12): : 3573 - 3577
  • [7] EXPERIENCE WITH SF6 GAS-INSULATED SUBSTATIONS AND PROPOSALS FOR IMPROVED RELIABILITY
    LINDSAY, C
    HICK, M
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1984, 103 (09): : 2596 - 2604
  • [8] Research progress on photoacoustic SF6 decomposition gas sensor in gas-insulated switchgear
    Yin, Xukun
    Su, Yongliang
    Xi, Teli
    Chen, Baisong
    Zhang, Le
    Zhang, Xueshi
    Liu, Lixian
    Shao, Xiaopeng
    JOURNAL OF APPLIED PHYSICS, 2022, 131 (13)
  • [9] Triangle Fault Diagnosis Method for SF6 Gas-Insulated Equipment
    Wu, Siying
    Zeng, Fuping
    Tang, Ju
    Yao, Qiang
    Miao, Yulong
    IEEE TRANSACTIONS ON POWER DELIVERY, 2019, 34 (04) : 1470 - 1477
  • [10] Study on the aging characteristics of PET for SF6 gas-insulated transformer
    Zhang, Daning
    Xu, Haisong
    Yang, Dingqian
    Wang, Qian
    Mu, Haibao
    Zhang, Guanjun
    AIP ADVANCES, 2024, 14 (07)