Application of TCR-Type SVC in Power Substation and Electric Arc Furnaces

被引:0
作者
Zhao, ZhongYuan [1 ]
Chen, ChiHan [1 ]
Bao, ShunXian [1 ]
Fang, TaiXun [1 ]
Wang, XiaoHong [1 ]
机构
[1] NanJing NARI RELAYS Elect Co Ltd, Nanjing 211102, Peoples R China
来源
2010 IEEE PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION: SMART SOLUTIONS FOR A CHANGING WORLD | 2010年
关键词
SVC; voltage fluctuation and flicker; harmonic mitigation; electric arc furnace;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The situation at electric arc furnace factory is always severe containing voltage fluctuation and flicker, three-phase imbalance and low power factor. The dynamic var compensator is a good solution to this condition. The svc, with its continuously variable compensation, also safeguards the plant against overcompensation during furnace outages. The svc equipment, offered by NARI-RELAYS, presents a phase-wise open-loop reactive power controller and a three-phase closed-loop power factor control, which are based on high-speed space vector control. The factory system test on physical simulator is implemented, and its open-loop response time is less than 7 milliseconds with closed-loop one less than 25 milliseconds. One electric arc furnace plant engineering is illustrated as an example to show the effects with/without SVC function. Meanwhile, the voltage fluctuation depression is also shown with SVC operation applied in a power substation.
引用
收藏
页数:4
相关论文
共 6 条
[1]  
DING RJ, 2006, T CHINA ELECTROTECHN, V21, P48
[2]  
Ji F. F., 2005, P CHINESE SOC ELECT, V25, P27
[3]  
LI XG, 2001, POWER SYSTEM TECHNOL, V25, P288
[4]  
Sun Chi, 2003, Proceedings of the CSEE, V23, P43
[5]  
Wang Mao-hai, 2003, Proceedings of the CSEE, V23, P56
[6]   Valuation of dynamic reactive power support services for transmission access [J].
Xu, WS ;
Zhang, Y ;
da Silva, LCP ;
Kundur, P ;
Warrack, AA .