Analysis and Optimization of Cooling Water System Operating Cost under Changes in Ambient Temperature and Working Medium Flow

被引:5
作者
Wang, Peng [1 ]
Lu, Jinling [1 ]
Cai, Qingsen [1 ]
Chen, Senlin [1 ]
Luo, Xingqi [1 ]
机构
[1] Xian Univ Technol, Inst Water Resources & Hydropower, State Key Lab Base Ecohydraul Engn Arid Area, Xian 710048, Peoples R China
基金
中国国家自然科学基金;
关键词
circulating cooling water system; operating cost; ambient temperature; working medium flow; optimization model; optimal water supply temperature; DESIGN; NETWORKS; PUMP; PERFORMANCE; COOLER;
D O I
10.3390/en14216903
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The circulating cooling water system is widely used in various industrial production fields, and its operating cost largely depends on external factors, such as ambient temperature and working medium flow. Considering the relative elevation of the heat exchanger, this study establishes a total system operation cost analysis and optimization model based on the superstructure method. The model uses ambient dry bulb temperature, ambient wet bulb temperature, and working medium flow as random variables. Water supply temperature is adopted as the decision variable, and the minimum operating cost of the system is used as the objective function. An analysis of the effect of the three random variables on the operation cost shows that the effect of ambient dry bulb temperature on the operation cost is negligible, and the effect of ambient wet bulb temperature and working medium flow on the operation cost is significant. In addition, a control equation of water supply temperature is established to determine the "near optimal " operation, which is based on the correlation among ambient wet bulb temperature, working medium flow, and optimal water supply temperature. Then, the method is applied to a case system. The operating cost of the system is reduced by 22-31% at different times during the sampling day.
引用
收藏
页数:19
相关论文
共 34 条
[21]   Application of an environmentally optimum cooling water system design to water and energy conservation [J].
Panjeshahi, M. H. ;
Ataei, A. .
INTERNATIONAL JOURNAL OF ENVIRONMENTAL SCIENCE AND TECHNOLOGY, 2008, 5 (02) :251-262
[22]   Pressure drop optimisation in debottlenecking of heat exchanger networks [J].
Panjeshahi, Mohammad Hassan ;
Tahouni, Nassim .
ENERGY, 2008, 33 (06) :942-951
[23]   Thermodynamic study of the effects of ambient air conditions on the thermal performance characteristics of a closed wet cooling tower [J].
Papaefthimiou, V. D. ;
Rogdakis, E. D. ;
Koronaki, I. P. ;
Zannis, T. C. .
APPLIED THERMAL ENGINEERING, 2012, 33-34 :199-207
[24]  
Perry R., 1997, PERRYS CHEM ENG HDB, V7th
[25]  
POLLEY GT, 1991, CHEM ENG RES DES, V69, P445
[26]   Analysis of the effect of seasonal climate changes on cooling tower efficiency, and strategies for reducing cooling tower power consumption [J].
Pontes, Ricardo F. F. ;
Yamauchi, Willian M. ;
Silva, Evelin K. G. .
APPLIED THERMAL ENGINEERING, 2019, 161
[27]   Pump network optimization for a cooling water system [J].
Sun, Jin ;
Feng, Xiao ;
Wang, Yufei ;
Deng, Chun ;
Chu, Khim Hoong .
ENERGY, 2014, 67 :506-512
[28]  
Suo R., 2015, COMPUT APPL CHEM, V32, P1439
[29]   A simultaneous methodology for the optimal design of integrated water and energy networks considering pressure drops in process industries [J].
Torkfar, Fardin ;
Avami, Akram .
PROCESS SAFETY AND ENVIRONMENTAL PROTECTION, 2016, 103 :442-454
[30]  
Yu J., 2006, Principle and design of heat exchangers