Validation of a computer model for solar assisted district heating systems with seasonal hot water heat store

被引:61
作者
Raab, S
Mangold, D
Müller-Steinhagen, H
机构
[1] Univ Stuttgart, ITW, D-70550 Stuttgart, Germany
[2] SWT, Stuttgart, Germany
[3] ITT, DLR, Stuttgart, Germany
关键词
solar assisted district heating; heat store; validation; TRNSYS;
D O I
10.1016/j.solener.2004.10.014
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The TRNSYS XST-model for the calculation of the thermal behaviour of ground buried hot water heat stores was validated. For the validation procedure measured data of the seasonal hot water heat store in Hannover (Germany) were used. In contrast to previous investigations the temperatures of the surrounding ground were also taken into consideration. The determination of the heat store parameters was carried out using TRNSYS in combination with the parameter identification software DF. The deviation between measured and calculated temperatures is less than +/- 3%. The measured and calculated heat quantities are also in good agreement (annual deviation less than 2%). The validated XST-model was integrated into a TRNSYS model to calculate the thermal behaviour of the solar assisted district heating system in Hannover in 2002. The deviations between measured and calculated heat quantities do not exceed 5%. (c) 2005 Elsevier Ltd. All rights reserved.
引用
收藏
页码:531 / 543
页数:13
相关论文
共 15 条
[1]  
[Anonymous], TRANS SYST SIM PROGR
[2]  
BODMANN M, 2004, P ISES EUR SOL C FRE, V1, P137
[3]  
Dalenback JO, 1993, SOLAR HEATING SEASON
[4]  
ENNER M, 2004, SOLAR UNTERTUTZTE NA
[5]  
ESKILSON P, 2000, EARTH ENERGY DESIGNE
[6]  
Geiger B, 2002, BWK, V54, P50
[7]  
ISAKSON P, 1993, MFC 1 0BETA MATCHED
[8]  
JOHN R, 2002, THESIS U MARBURG MAR
[9]  
MAZZARELLA L, 1991, P THERM SCHEV NETH
[10]  
MAZZARELLA L, 1994, MULTIFLOW STRATIFIED