Experimental study on a new internally cooled/heated dehumidifier/regenerator of liquid desiccant systems

被引:135
作者
Yin, Yonggao [1 ]
Zhang, Xiaosong [1 ]
Wang, Geng [1 ]
Luo, Lei [1 ]
机构
[1] Southeast Univ, Sch Energy & Environm, Nanjing 210096, Jiangsu, Peoples R China
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2008年 / 31卷 / 05期
基金
中国国家自然科学基金;
关键词
air conditioning; dehumidifier; desiccant; design; heat exchanger; regenerator; finned tube; experiment;
D O I
10.1016/j.ijrefrig.2007.10.004
中图分类号
O414.1 [热力学];
学科分类号
摘要
For providing good performance of dehumidifier and regenerator with certain dimensions, a new type of internally cooled/heated dehumidifier/regenerator based on the plate-fin heat exchanger (PFHE) was designed. To investigate the behavior of the new equipment, an experimental setup was established in an environment chamber with regulable temperature and humidity air. By the internally cooled dehumidification testing, effects of the cooling waiter temperature, the air flow rate and the desiccant temperature on the dehumidification performance and the cooling efficiency were presented. The behavior of internally cooled dehumidification process was compared with that of the adiabatic dehumidification process. The results suggested that the cooling efficiency decreased with the increasing of the cooling water temperature and desiccant with low temperature could bring more mass transfer coefficients. There is an optimal air flow rate to achieve the maximum absolute humidity decrease of the air. By the internally heated regeneration testing, effects of the air flow rate and the desiccant inlet temperature on the regeneration performance and air outlet parameters were discussed and also compared with those of the adiabatic regeneration process. It was concluded that the regeneration efficiency of internally heated regeneration was more than that of the adiabatic regeneration, and the internally heated regenerator could offer better thermal performance. (C) 2007 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:857 / 866
页数:10
相关论文
共 50 条
  • [21] Experimental study of the film thickness in the dehumidifier of a liquid desiccant air conditioning system
    Luo, Yimo
    Wang, Meng
    Yang, Hongxing
    Lu, Lin
    Peng, Jinqing
    ENERGY, 2015, 84 : 239 - 246
  • [22] Experimental study on mass transfer performances of cross flow dehumidifier using liquid desiccant
    Liu, X. H.
    Zhang, Y.
    Qu, K. Y.
    Jiang, Y.
    ENERGY CONVERSION AND MANAGEMENT, 2006, 47 (15-16) : 2682 - 2692
  • [23] Optimization of NTUm allocation between dehumidifier and regenerator in liquid-desiccant air-conditioning system
    Guan, Bowen
    Liu, Xiaohua
    Zhang, Tao
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2021, 127 : 250 - 259
  • [24] Experimental performance analysis and simulation of an internally cooled liquid desiccant air conditioning system using a novel ionic liquid
    Varela, Richard Jayson
    Yamaguchi, Seiichi
    Giannetti, Niccolo
    Saito, Kiyoshi
    Wang, Xin-Ming
    Nakayama, Hiroshi
    14TH IIR GUSTAV-LORENTZEN CONFERENCE ON NATURAL FLUIDS, 2020, : 304 - 309
  • [25] Energy Consumption of Solar-assisted Internally Cooled/Heated Liquid Desiccant Air-conditioning System in Hong Kong
    Qi Ronghui
    Lu Lin
    INTERNATIONAL CONFERENCE ON APPLIED ENERGY, ICAE2014, 2014, 61 : 2686 - 2689
  • [26] On the importance of the heat and mass transfer resistances in internally-cooled liquid desiccant dehumidifiers and regenerators
    Woods, Jason
    Kozubal, Eric
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2018, 122 : 324 - 340
  • [27] Experimental investigation of the regeneration performance of an internally heated regenerator used for heating tower solution regeneration
    Song, Pengyuan
    Xiao, Hansong
    Wang, Baolong
    Shi, Wenxing
    Li, Xianting
    Zhang, Guohui
    ENERGY CONVERSION AND MANAGEMENT, 2019, 189 : 184 - 194
  • [28] Performance study on a structured packed liquid desiccant regenerator
    Elsarrag, Esam
    SOLAR ENERGY, 2006, 80 (12) : 1624 - 1631
  • [29] Study on the performance of celdek packed counter flow liquid desiccant regenerator
    Kumar, Rakesh
    Asati, Arun Kumar
    JOURNAL OF MECHANICAL SCIENCE AND TECHNOLOGY, 2017, 31 (09) : 4489 - 4498
  • [30] Study on the performance of celdek packed counter flow liquid desiccant regenerator
    Rakesh Kumar
    Arun Kumar Asati
    Journal of Mechanical Science and Technology, 2017, 31 : 4489 - 4498