Municipal reclaimed water as makeup water for cooling systems: Water efficiency, biohazards, and reliability

被引:10
作者
Badruzzaman, Mohammad [1 ]
Anazi, Jasem R. [1 ]
Al-Wohaib, Fawaz A. [1 ]
Al-Malki, Abdulaziz A. [2 ]
Jutail, Fadel [3 ]
机构
[1] Saudi Aramco, Environm Protect, Dhahran, Saudi Arabia
[2] Saudi Aramco, Proc & Control Syst Dept, Dhahran, Saudi Arabia
[3] Saudi Aramco, Community Serv Dept, Dhahran, Saudi Arabia
关键词
Cooling tower; Reclaimed water; Cycle of concentration; Make-up water; Water efficiency; Biohazards; REUSE;
D O I
10.1016/j.wri.2022.100188
中图分类号
TV21 [水资源调查与水利规划];
学科分类号
081501 ;
摘要
Municipal reclaimed water is increasingly being considered as a sustainable source of makeup water for cooling towers. However, many oil and gas facilities in the water scarce middle eastern regions still depend on non-renewable groundwater for operating cooling towers. Successful application of reclaimed water in a dry desert climate with very high temperature requires a critical understanding of several factors, including water efficiency, biohazards, equipment reli-ability, and economics. In particular, biohazard assessment, due to bacteria and virus contami-nation in hot weather, should be assessed to understand the human risks of utilizing reclaimed water. This study investigated the applicability of municipal reclaimed water as an alternative to groundwater for an industrial cooling system at an oil and gas facility in Saudi Arabia. Treated wastewater effluent from an activated sludge biological treatment process was utilized, as make up water for a 4.2 MW cooling tower. The results of this study showed that water efficiency can be increased using municipal reclaimed water instead of groundwater by increasing the cycle of concentration. The bacterial and enteric virus study indicated that the disinfection and biocide treatment was effective in controlling biological growth and minimizing associated risks to human health. The use of reclaimed water was economically viable with 27% reduction in water consumption.
引用
收藏
页数:13
相关论文
共 23 条
  • [11] Reuse and recycling of secondary effluents in refineries employing advanced multi-barrier systems
    Lahnsteiner, J.
    Mittal, R.
    [J]. WATER SCIENCE AND TECHNOLOGY, 2010, 62 (08) : 1813 - 1820
  • [12] Escalating Water Demand for Energy Production and the Potential for Use of Treated Municipal Wastewater
    Li, Heng
    Chien, Shih-Hsiang
    Hsieh, Ming-Kai
    Dzombak, David A.
    Vidic, Radisav D.
    [J]. ENVIRONMENTAL SCIENCE & TECHNOLOGY, 2011, 45 (10) : 4195 - 4200
  • [13] Munson R., 2009, DOENETL311040609
  • [14] Nguyen TMN, 2006, J INFECT DIS, V193, P102, DOI 10.1086/498575
  • [15] Oppenheimer J, 2015, DRIVERS SUCCESSES CH
  • [16] Overton, 2015, TAMPA ELECT COS POLK
  • [17] Puckorius P, 2013, CONSIDER RECYCLED WA
  • [18] San Diego County Water Authority, 2009, TECHN INF COOL US RE
  • [19] Transitioning to zero freshwater withdrawal in the US for thermoelectric generation
    Tidwell, Vincent C.
    Macknick, Jordan
    Zemlick, Katie
    Sanchez, Jasmine
    Woldeyesus, Tibebe
    [J]. APPLIED ENERGY, 2014, 131 : 508 - 516
  • [20] The cooling tower water microbiota: Seasonal dynamics and co-occurrence of bacterial and protist phylotypes
    Tsao, Han-Fei
    Scheikl, Ute
    Herbold, Craig
    Indra, Alexander
    Walochnik, Julia
    Horn, Matthias
    [J]. WATER RESEARCH, 2019, 159 : 464 - 479