Bayesian Optimization-Based Gradient Boosting Method of Fault Detection in Oil-Immersed Transformer and Reactors

被引:21
作者
Paul, Devaprasad [1 ]
Goswarmi, Arup Kumar [1 ]
Chetri, Rahul Lamichane [1 ]
Roy, Rajesh [1 ]
Sen, Pritin [2 ]
机构
[1] Natl Inst Technol Silchar, Silchar 788010, India
[2] Power Grid Corp India Ltd, Gurgaon 78247, India
关键词
Gases; Oils; Oil insulation; Inductors; Power transformer insulation; Discharges (electric); Fault detection; Bayesian optimization (BO); dissolved gas analysis (DGA); fault detection; gradient boosting (GB); insulating oil; DISSOLVED-GAS ANALYSIS; IEC TC 10; POWER TRANSFORMERS; INCIPIENT FAULTS; DIAGNOSIS; PREDICTION; NETWORKS; TOOL;
D O I
10.1109/TIA.2021.3134140
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This article aims at developing a gradient boosting (GB) model with parameters optimized by the Bayesian optimization (BO) method for detecting various types of fault in an oil-immersed transformer and reactor. The developed model depicts higher accuracy in comparison with other machine learning (ML) techniques, such as XGBoost, AdaBoost, random forest, and support vector machine parameters being optimized by BO. A comparison of the skill score depicts the superiority of the developed Bayesian optimization-based gradient boosting (BO-GB) model with respect to Bayesian optimized other ML techniques. Further comparison of the model with conventional Duval pentagon verifies the accuracy of detecting the faults, which were missed by the former. Also, the software has been developed based on the proposed BO-GB method for the on-site detection of the fault. In addition, actual values of dissolved gases with respect to fault confirmed after the internal inspection of the transformer and reactor are tabulated and compared. The data so presented will help in utilizing the authentic dissolved gas data in addition to the already available IEC TC10 databases for future works. The study undertaken in this article will help utilities in diagnosing the incipient faults more accurately and precisely, thereby preventing hazardous operating conditions along with minimizing the downtime cost.
引用
收藏
页码:1910 / 1919
页数:10
相关论文
共 53 条
[1]   A Review of Dissolved Gas Analysis Measurement and Interpretation Techniques [J].
Abu Bakar, Norazhar ;
Abu-Siada, A. ;
Islam, S. .
IEEE ELECTRICAL INSULATION MAGAZINE, 2014, 30 (03) :39-49
[2]  
[Anonymous], 2005, 60567 IEC
[3]  
[Anonymous], 2015, Mineral Oil-Filled Electrical Equipment in Service-Guidance on the Interpretation of Dissolved and Free Gases Analysis
[4]  
Bergstra J.S., 2011, ADV NEURAL INFORM PR
[5]   Random forests [J].
Breiman, L .
MACHINE LEARNING, 2001, 45 (01) :5-32
[6]   Bayesian Networks applied to Failure Diagnosis in Power Transformer [J].
Carita, A. J. Q. ;
Leite, L. C. ;
Junior, A. P. P. M. ;
Godoy, R. B. ;
Sauer, L. .
IEEE LATIN AMERICA TRANSACTIONS, 2013, 11 (04) :1075-1082
[8]   Improvement of Power Transformer Insulation Diagnosis Using Oil Characteristics Data Preprocessed by SMOTEBoost Technique [J].
Cui, Yi ;
Ma, Hui ;
Saha, Tapan .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2014, 21 (05) :2363-2373
[9]   A review of monitoring methods for predictive maintenance of electric power transformers based on dissolved gas analysis [J].
de Faria, Haroldo, Jr. ;
Spir Costa, Joao Gabriel ;
Mejia Olivas, Jose Luis .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2015, 46 :201-209
[10]   A gradient boosting logit model to investigate driver's stop-or-run behavior at signalized intersections using high-resolution traffic data [J].
Ding, Chuan ;
Wu, Xinkai ;
Yu, Guizhen ;
Wang, Yunpeng .