Optimization of return vent height for stratified air distribution system with impinging jet supply satisfying threshold of |PMV| < 0.5

被引:25
|
作者
Qin, Chao [1 ]
Zhou, Wei-Ru [2 ]
Fang, Hong-Qiang [1 ]
Lu, Wei-Zhen [1 ]
Lee, Eric Wm [1 ]
机构
[1] City Univ Hong Kong, Dept Architecture & Civil Engn, Hong Kong, Peoples R China
[2] Chiaphua Components Grp, Ind & Consumer Team, Shenzhen 518000, Guangdong, Peoples R China
关键词
Stratified air distribution systems; Impinging jet supply; Return vent height; Cooling coil load; Thermal comfort; THERMAL COMFORT; ENERGY-CONSUMPTION; INDOOR ENVIRONMENT; COOLING LOAD; STRATUM VENTILATION; PERFORMANCE; FLOW; PREDICTION; ROOM; SIMULATION;
D O I
10.1016/j.jclepro.2022.132033
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
The stratified air distribution (STRAD) ventilation system addresses much attention due to the less cooling energy consumption than conventional mixing ventilation systems in maintaining a proper indoor environment. In recent literature, the vent height of STRAD systems has been studied. However, in previous studies, the impacts of over-cooling and/or over-warming on cooling load as well as, consequently, on the optimal return vent height were not systematically considered. In practice, the indoor environment (e.g., predictive mean vote PMV, indoor air quality IAQ) is sensitive to the supply condition (e.g., supply temperature) and the return vent height. This study aims to optimize the return vent height of a STRAD ventilation system with impinging jet supply under a general thermal comfort condition, i.e., threshold of vertical bar PMV vertical bar < 0.5. The evaluated indices include the cooling coil load, the temperature difference between the head and ankles, the average CO2 concentration, the average mean age of air, and the predicted percentage of dissatisfied. The research outcomes indicate that: a) the increase of supply temperature generally avoids overcooling and reduces cooling coil load; b) the cooling coil load increases and c) the IAQ generally upgrades as the return vent height rises; d) the optimal return vent height with the impinging jet ventilation is recommended as 2.625 m (i.e., near the ceiling), which is different from previously suggested mid-level return vent. Under this optimal return vent height, the supply temperature can be increased to 22 degrees C with resultant vertical bar PMV vertical bar < 0.5, lower cooling coil load, and better IAQ comparing to the recommended case of mid-level return vent with a supply temperature of 18 degrees C.
引用
收藏
页数:15
相关论文
共 7 条
  • [1] Establishing multi-criteria optimization of return vent height for underfloor air distribution system
    Qin, Chao
    Fang, Hong-Qiang
    Wu, Shi-Hai
    Lu, Wei-Zhen
    JOURNAL OF BUILDING ENGINEERING, 2022, 57
  • [2] The impacts of evaluation indices and normalization methods on E-TOPSIS optimization of return vent height for an impinging jet ventilation system
    Qin, Chao
    Wu, Shi-Hai
    Fang, Hong-Qiang
    Lu, Wei-Zhen
    BUILDING SIMULATION, 2022, 15 (12) : 2081 - 2095
  • [3] Optimization study of return vent height for an impinging jet ventilation system with exhaust/return-split configuration by TOPSIS method
    Ye, Xiao
    Kang, Yanming
    Yan, Zhenrong
    Chen, Bin
    Zhong, Ke
    BUILDING AND ENVIRONMENT, 2020, 177
  • [4] Optimizing the Return Vent Height for Improved Performance in Stratified Air Distribution Systems
    Qiao, Danping
    Wu, Shihai
    Zhang, Nan
    Qin, Chao
    BUILDINGS, 2024, 14 (04)
  • [5] The impacts of evaluation indices and normalization methods on E-TOPSIS optimization of return vent height for an impinging jet ventilation system
    Chao Qin
    Shi-Hai Wu
    Hong-Qiang Fang
    Wei-Zhen Lu
    Building Simulation, 2022, 15 : 2081 - 2095
  • [6] Effects of return air vent height on energy consumption, thermal comfort conditions and indoor air quality in an under floor air distribution system
    Heidarinejad, Ghassem
    Fathollahzadeh, Mohammad Hassan
    Pasdarshahri, Hadi
    ENERGY AND BUILDINGS, 2015, 97 : 155 - 161
  • [7] Multi-objective optimization of supply air inlet structure for impinging jet ventilation system based on radial basis function neural network
    Wang, Chen
    Hu, Ke
    Liu, Yin
    CASE STUDIES IN THERMAL ENGINEERING, 2025, 65