Partial discharge detection for GIS using narrow band ultra-high-frequency (UHF) method

被引:2
|
作者
Sun, YZ [1 ]
Yin, H [1 ]
Zhang, QG [1 ]
Yu, FS [1 ]
Wang, H [1 ]
Qiu, YC [1 ]
机构
[1] Henan Polytech Univ, Sch Elect Engn, Jiaozuo 454100, Peoples R China
关键词
GIS; partial discharge; UHF;
D O I
10.1109/ISEIM.2005.193479
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Partial discharge (PD) detection is an effective means for monitoring and evaluation of dielectric condition of gas insulated system (GIS). The conventional PD detection methods are too susceptible to disturbances and unsuitable for on-line monitoring. The ultra-high-frequency (UHF) PD detection technique can detect and locate the PD sources inside GIS by detecting electromagnetic wave emitted from PD source The narrow band UHF method was emphasized in this paper, because it can void the electromagnetic interference by selecting the appropriate frequency. A PD detection system using narrow band UHF method was designed. The typical defects that can cause partial discharge in GIS were simulated in laboratory. Using this detection system the PD waveform of frequency domain and time domain could be gotten. The results show that the time domain waveforms of the same defect have very similar distribution characteristics and those of different defect have different ones. So it would be very convenient for the recognition of PD types.
引用
收藏
页码:748 / 751
页数:4
相关论文
共 50 条
  • [21] Development of multi-band ultra-high-frequency sensor for partial discharge monitoring based on the meandering technique
    Ye Hai-feng
    Qian Yong
    Dong Yue
    Sheng Ge-hao
    Jiang Xiu-chen
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2014, 8 (05) : 327 - 335
  • [22] Detection and Analysis of Partial Discharge using Ultra High Frequency Sensor
    Reddy, P. Gurumurthy
    Kundu, Prasanta
    2014 ANNUAL INTERNATIONAL CONFERENCE ON EMERGING RESEARCH AREAS: MAGNETICS, MACHINES AND DRIVES (AICERA/ICMMD), 2014,
  • [23] Experimental Investigation of Partial Discharge Detection in Medium-voltage Switchgear Based on Ultra-High-Frequency Sensor
    Wang, Liuhuo
    Ning, Wenjun
    Wang, Lijun
    Lu, Hong
    Wang, Haijing
    Jia, Shenli
    Wu, Ji
    2013 2ND INTERNATIONAL CONFERENCE ON ELECTRIC POWER EQUIPMENT - SWITCHING TECHNOLOGY (ICEPE-ST), 2013,
  • [24] Internal UHF antenna for partial discharge detection in GIS
    Bin, Feng
    Wang, Feng
    Sun, Qiuqin
    Lin, Shu
    Xie, Yaoheng
    Fan, Min
    IET MICROWAVES ANTENNAS & PROPAGATION, 2018, 12 (14) : 2184 - 2190
  • [25] The application of ultra-high-frequency partial discharge measurements to gas-insulated substations
    Kurrer, R
    Feser, K
    IEEE TRANSACTIONS ON POWER DELIVERY, 1998, 13 (03) : 777 - 782
  • [26] An Intelligent Sensor for the Ultra-High-Frequency Partial Discharge Online Monitoring of Power Transformers
    Li, Jian
    Li, Xudong
    Du, Lin
    Cao, Min
    Qian, Guochao
    ENERGIES, 2016, 9 (05)
  • [27] Study of UHF frequency response characteristics of the inner sensor for partial discharge detection in GIS
    Tang, Ju
    Shi, Haijun
    Sun, Caixin
    Wei, Gang
    Zhu, Wei
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2004, 19 (05): : 71 - 75
  • [28] Partial Discharge Localization in Transformers Using UHF Detection Method
    Sinaga, H. H.
    Phung, B. T.
    Blackburn, T. R.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2012, 19 (06) : 1891 - 1900
  • [29] Study of comparison between Ultra-high Frequency (UHF) method and ultrasonic method on PD detection for GIS
    Li, Yanran
    Chen, Duo
    Li, Li
    Zhang, Jiwei
    Li, Guang
    Liu, Hongxia
    2017 3RD INTERNATIONAL CONFERENCE ON ENERGY, ENVIRONMENT AND MATERIALS SCIENCE (EEMS 2017), 2017, 94
  • [30] Ultra-high-frequency (UHF) PD measuring system for power transformer
    Wang, G.L.
    Hao, Y.B.
    Liu, W.G.
    Li, Y.M.
    2001, Science Press (27):