On the use of transmission line theory to represent a nonuniform vertically-extended object struck by lightning

被引:0
|
作者
Bermudez, JL [1 ]
Rachidi, F [1 ]
Chisholm, WA [1 ]
Rubinstein, M [1 ]
Janischewskyj, W [1 ]
Hussein, AM [1 ]
Shostak, V [1 ]
Chang, JS [1 ]
机构
[1] Swiss Fed Inst Technol, CH-1015 Lausanne, Switzerland
来源
2003 IEEE SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY, SYMPOSIUM RECORD, VOLS 1 AND 2 | 2003年
关键词
Lightning; Instrumented Tower; Reduced-Scale Models (RSM); elevated strike object (ESO); transmission line (TL) model;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this study, we present an experimental validation of the transmission line representation of an elevated object struck by lightning. The experimental results are obtained using a reduced-scale model and injected signals with narrow pulse widths (down to 500 ps). The validation is performed using a reduced scale structure representing the Toronto CN Tower in Canada. Two models consisting, respectively, of 1-section and 3-section uniform transmission lines were considered for the comparison. It is shown that the 3-section model is able to accurately reproduce the obtained experimental data. The overall agreement between the 1-section model and the experimental results is also satisfactory, at least for the early-time response.
引用
收藏
页码:501 / 504
页数:4
相关论文
共 29 条
  • [1] AN EQUIVALENT CIRCUIT OF A TRANSMISSION-LINE TOWER STRUCK BY LIGHTNING
    Hashimoto, Soh
    Baba, Yoshihiro
    Nagaoka, Naoto
    Ametani, Akihiro
    Itamoto, Naoki
    2010 30TH INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP), 2010,
  • [3] Measurement of lightning surges on test transmission line equipped with arresters struck by natural and triggered lightning
    Hokuriku Electric Power Co, Toyama, Japan
    IEEE Trans Power Delivery, 2 (996-1002):
  • [4] Measurement of lightning surges on test transmission line equipped with arresters struck by natural and triggered lightning
    Matsumoto, Y
    Sakuma, O
    Shinjo, K
    Saiki, M
    Wakai, T
    Sakai, T
    Nagasaka, H
    Motoyama, H
    Ishii, M
    IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (02) : 996 - 1002
  • [5] Modeling of Corona Discharge on a Transmission Line Conductor Struck by Lightning for FDTD Calculations
    Tran Huu Thang
    Baba, Yoshihiro
    Nagaoka, Naoto
    Ametani, Akihiro
    Takami, Jun
    Okabe, Shigemitsu
    Rakov, Vladimir A.
    2010 ASIA-PACIFIC INTERNATIONAL SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY & TECHNICAL EXHIBITION ON EMC RF/MICROWAVE MEASUREMENTS & INSTRUMENTATION, 2010, : 1309 - 1312
  • [6] Effect of vertically extended strike object on the distribution of current along the lightning channel
    Rachidi, F
    Rakov, VA
    Nucci, CA
    Bermudez, JL
    JOURNAL OF GEOPHYSICAL RESEARCH-ATMOSPHERES, 2002, 107 (D23)
  • [7] Analytical solutions in nonuniform multiconductor transmission line theory
    Nitsch, J
    Gronwald, F
    IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 1999, 41 (04) : 469 - 479
  • [8] Generalized transmission-line theory for the treatment of nonuniform multiconductor transmission lines
    Haase, H
    Nitsch, H
    INTERNATIONAL JOURNAL OF APPLIED ELECTROMAGNETICS AND MECHANICS, 2003, 17 (1-3) : 149 - 156
  • [9] On the Evaluation of the Voltage Rise on Transmission Line Tower Struck by Lightning Using Electromagnetic and Circuit-Based Analyses
    Saito, Mikihisa
    Ishii, Masaru
    Miki, Megumu
    Tsuge, Kenji
    IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (02) : 627 - 638
  • [10] Band-Stop Behavior Vertically Extended Ground Isolator Based on Transmission Line Theory for IBFD TRx Decoupling Applications
    Yoon, Taeyeong
    Park, Uichan
    Oh, Jungsuek
    IEEE TRANSACTIONS ON MICROWAVE THEORY AND TECHNIQUES, 2024, 72 (02) : 1405 - 1415