Thermal performance of flat vapor chamber heat spreader

被引:79
作者
Hsieh, Shou-Shing [1 ]
Lee, Ron-Yu [1 ]
Shyu, Jin-Cherng [2 ]
Chen, Shao-Wen [2 ]
机构
[1] Natl Sun Yat Sen Univ, Dept Mech & Electromech Engn, Kaohsiung 80424, Taiwan
[2] Ind Technol Res Inst, Microsyst Technol Ctr, Tainan 70955, Taiwan
关键词
IC cooling technology; vapor chamber heat spreader; evaporation and condensation;
D O I
10.1016/j.enconman.2007.10.024
中图分类号
O414.1 [热力学];
学科分类号
摘要
Experiments were performed to examine the spreading thermal resistance of centrally positioned heat sources and the thermal performance of a water charged, gravity assisted flat vapor chamber to be used for electronic cooling. Parametric studies including different heat fluxes and operating temperatures were conducted, and the effect of the relevant parameters on the cooling performance in terms of the spreading resistance was presented and discussed. The present vapor chamber heat spreader showed a heat removal capacity of 220 W/cm(2) with a thermal spreading resistance of 0.2 degrees C/W. (C) 2007 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1774 / 1784
页数:11
相关论文
共 7 条