A multi-additive suppressant agent-based low-flow and long-distance firefighting approach for suppressing wildfires near electrical transmission lines

被引:6
作者
Lu, JiaZheng [1 ]
Chen, Bao-Hui [1 ,2 ]
Wu, ChuanPing [1 ]
Liu, Xing [1 ]
Zhou, TeJun [1 ]
Tan, YanJun [1 ]
机构
[1] Hunan Elect Power Corp Disaster Prevention & Redu, State Key Lab Disaster Prevent & Reduct Power Gri, State Grid Key Lab Power Transmiss & Distribut Eq, Changsha 410007, Hunan, Peoples R China
[2] Hunan Univ, Coll Elect & Informat Engn, Changsha, Hunan, Peoples R China
基金
中国博士后科学基金;
关键词
Wildfire suppression; transmission lines; high lift; suppressant agent; suppression additive; low flow; high pressure; water mist; mist nozzle; WATER MIST SUPPRESSION; FIRES; PERFORMANCE; EFFICIENCY; SYSTEM;
D O I
10.1177/0734904116659499
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
The key challenges of the wildfire firefighting were long-distanced and high-lifted fire events and limited water access in wildlands. This article proposed a new low-flow and high-lift firefighting approach for the application of wildfire near transmission lines. To solve the challenges, we developed a comprehensive firefighting equipment set which consisted of a high-effective suppressant agent with properties to prevent reignition and a mobile firefighting platform with long-distance and high-lift features. The liquid suppression agent improved the effectiveness of fire suppression while reducing the consumption of water significantly. As the hydraulic flow was decreased for a given volume of water, the hydraulic pressure was increased. In this way, the platform can produce a hydraulic pressure over 120bar for an effective lift of 500m. The results of field experiments demonstrated that the proposed approach is able to control wildfires over a long distance and high lift, which proved the effectiveness of the approach.
引用
收藏
页码:398 / 415
页数:18
相关论文
共 31 条
[1]   A GIS-based decision support system for determining the shortest and safest route to forest fires: a case study in Mediterranean Region of Turkey [J].
Akay, Abdullah E. ;
Wing, Michael G. ;
Sivrikaya, Fatih ;
Sakar, Dursun .
ENVIRONMENTAL MONITORING AND ASSESSMENT, 2012, 184 (03) :1391-1407
[2]  
ANNAKUTTY KS, 1991, MAKROMOL CHEM, V192, P11
[3]  
[Anonymous], FIRE SAFETY SCI
[4]  
[Anonymous], 2007, ASTM D4442-07, P6
[5]   Suppression of methane/air explosion by ultrafine water mist containing sodium chloride additive [J].
Cao, Xingyan ;
Ren, Jingjie ;
Zhou, Yihui ;
Wang, Qiuju ;
Gao, Xuliang ;
Bi, Mingshu .
JOURNAL OF HAZARDOUS MATERIALS, 2015, 285 :311-318
[6]   FIRE BEHAVIOR EXPERIMENTS IN MIXED FUEL COMPLEXES [J].
CATCHPOLE, EA ;
CATCHPOLE, WR ;
ROTHERMEL, RC .
INTERNATIONAL JOURNAL OF WILDLAND FIRE, 1993, 3 (01) :45-57
[7]   Surfactant-containing water mist suppression pool fire experimental analysis [J].
Chao Man ;
Zhu Shunbing ;
Jia Litao ;
Wu Xiaoli .
2014 INTERNATIONAL SYMPOSIUM ON SAFETY SCIENCE AND TECHNOLOGY, 2015, 84 :558-564
[8]  
Christian SD, 1997, HAL OPT TECHN WORK C, P88
[9]   Experimental Studies on Water Mist Suppression of Liquid Fires with and without Additives [J].
Cong, Beihua ;
Liao, Guangxuan .
JOURNAL OF FIRE SCIENCES, 2009, 27 (02) :101-123
[10]  
Darley Co. Ltd., 2016, DARL SNOW DRAG CH001