Corona-generated Space Charge Effects on Electric Field Distribution for an Indoor Corona Cage and a Monopolar Test Line

被引:33
作者
Bian, Xingming [1 ,2 ]
Yu, Deming [1 ,2 ]
Meng, Xiaobo [1 ,2 ]
MacAlpine, Mark [2 ]
Wang, Liming [2 ]
Guan, Zhicheng [1 ,2 ]
Yao, Wenjun [3 ]
Zhao, Shuzhen [3 ]
机构
[1] Tsinghua Univ, Dept Elect Engn, Beijing 100084, Peoples R China
[2] Tsinghua Univ, Grad Sch Shenzhen, Lab Adv Technol Elect Engn & Energy, Shenzhen 518055, Guangdong, Peoples R China
[3] N China Grid Co Ltd, Beijing Extra High Voltage Co, Beijing 102488, Peoples R China
基金
中国国家自然科学基金;
关键词
Positive corona; space charge; conductor; corona cage; test line; electric field; CONDUCTOR SURFACE CONDITIONS; VOLTAGE TRANSMISSION-LINES; HVDC TRANSMISSION; IONIZED FIELD; INTERFERENCE LEVEL; CURRENT-DENSITY; BIPOLAR CAGE; DISCHARGE; PREDETERMINATION; AVAILABILITY;
D O I
10.1109/TDEI.2011.6032849
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The effects of corona-generated space charge on the resultant electric field near a conductor were determined both for a simulated test line and a corona cage, since both are used in predicting the corona behavior of EHV and UHV transmission lines. Programs were developed for the calculation of the potential, the electric field and the space charge distributions for a simulated test line and a corona cage. Algorithms based on the charge simulation and the finite-element methods were used to solve Poisson's equation; and the method of characteristics to solve the current continuity equation. The resultant electric field on the ground plane of the two configurations was measured with a rotating field-mill, and the results fitted well with the calculated data. It was found the electric field at the surface of the conductor increased linearly, for both experimental configurations, before the voltage reached the corona inception value; but was reduced once corona-generated space charge was produced. The space charge and density distribution in the corona cage differed greatly from that around the test line: the electric field at the surface of the conductor in the test line decreased faster with voltage than that in the corona cage, the relative difference increasing as V-app/V-on was raised. The difference reached an asymptote of about 16% when the applied voltage was about 25% above the corona inception level.
引用
收藏
页码:1767 / 1778
页数:12
相关论文
共 37 条
  • [1] Abdel-Salam M., 2000, High-Voltage Engineering: Theory and Practice, V2nd
  • [2] NOVEL FINITE-ELEMENT ANALYSIS OF SPACE-CHARGE MODIFIED FIELDS
    ABDELSALAM, M
    ALHAMOUZ, Z
    [J]. IEE PROCEEDINGS-SCIENCE MEASUREMENT AND TECHNOLOGY, 1994, 141 (05) : 369 - 378
  • [3] ANALYSIS OF MONOPOLAR IONIZED FIELD AS INFLUENCED BY ION DIFFUSION
    ABDELSALAM, M
    ALHAMOUZ, Z
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1995, 31 (03) : 484 - 493
  • [4] A NEW FINITE-ELEMENT ANALYSIS OF AN IONIZED FIELD IN COAXIAL CYLINDRICAL GEOMETRY
    ABDELSALAM, MM
    ALHAMOUZ, ZM
    [J]. JOURNAL OF PHYSICS D-APPLIED PHYSICS, 1992, 25 (10) : 1551 - 1555
  • [5] Finite element computation of corona around monopolar transmission lines
    Al-Hamouz, Z
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 1998, 48 (01) : 57 - 63
  • [6] Corona power loss, electric field, and current density profiles in bundled horizontal and vertical bipolar conductors
    Al-Hamouz, ZM
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2002, 38 (05) : 1182 - 1189
  • [7] SPATIAL CHARACTERISTICS OF ELECTRIC-CURRENT AND FIELD IN LARGE DIRECT-CURRENT CORONAS
    ALLIBONE, TE
    JONES, JE
    SAUNDERSON, JC
    TAPLAMACIOGLU, MC
    WATERS, RT
    [J]. PROCEEDINGS OF THE ROYAL SOCIETY OF LONDON SERIES A-MATHEMATICAL PHYSICAL AND ENGINEERING SCIENCES, 1993, 441 (1911): : 125 - 146
  • [8] Influence of Aged Conductor Surface Conditions on AC Corona Discharge With a Corona Cage
    Bian, Xingming
    Yu, Deming
    Chen, Lan
    MacAlpine, J. M. K.
    Wang, Liming
    Guan, Zhicheng
    Chen, Fangdong
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2011, 18 (03) : 809 - 818
  • [9] PARAXIAL CORONA DISCHARGE .2. SIMULATION AND ANALYSIS
    BOUZIANE, A
    HIDAKA, K
    JONES, JE
    ROWLANDS, AR
    TAPLAMACIOGLU, MC
    WATERS, RT
    [J]. IEE PROCEEDINGS-SCIENCE MEASUREMENT AND TECHNOLOGY, 1994, 141 (03) : 205 - 214
  • [10] PARAXIAL CORONA DISCHARGE .1. REVIEW, INSTRUMENTATION AND EXPERIMENTS
    BOUZIANE, A
    HIDAKA, K
    JONES, JE
    ROWLANDS, AR
    TAPLAMACIOGLU, MC
    WATERS, RT