Detecting characteristics of SF6 decomposed gas sensor for insulation diagnosis on gas insulated switchgears

被引:27
作者
Okabe, Shigemitsu [1 ]
Kaneko, Shuhei [1 ]
Minagawa, Tadao [2 ]
Nishida, Chleko [2 ]
机构
[1] Tokyo Elect Power Co Ltd, Tsurumi Ku, Kanagawa 2308510, Japan
[2] Mitsubishi Electr Corp, Amagasaki, Hyogo 6618661, Japan
关键词
gas insulated switchgear (GIS); insulation diagnosis; partial discharge (PD) detection; SF6 decomposed gas; solid electrolyte sensor;
D O I
10.1109/T-DEI.2008.4446758
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Gas insulated switchgears (GISs) with SF6 gas with superior insulation and interruption performances used as an insulating medium have realized significant downsizing of substation facilities. GISs have been in use in substation facilities for more than 30 years and are expected to be used for an even longer period of time in the future. To realize effective operation and maintenance of highly aged apparatuses, it is necessary to establish insulation diagnosis technology that can be used to detect and accurately assess a discharge phenomenon occurring in a GIS. An effective diagnosis method. for the prevention of a facility contingency is to detect a partial discharge (PD) that occurs as a precursory phenomenon of dielectric breakdown. Whereas many of the diagnosis technologies for a PD are based on electrical measurements, the focus in this study was placed on the insulation diagnosis for decomposed gases generated by the energy of a discharge. Chemical measurements for detecting decomposed gases are less influenced by noise and more reliable than electrical measurements. Furthermore, an abnormality can be detected even if a PD does not occur at the time of measurement because decomposed gases build up. This method can also be applied to a fault location. This paper describes creating the prototypes of decomposed gas sensors based on solid electrolytes to detect fluoride gases. The sensors with different output types, i.e., "voltage-output type" and "current-output type", were examined. The "voltage-output type" is suited for diagnosis in a wide range of concentrations whereas the "current-output type" has a good detection sensitivity in a low-concentration range. Furthermore, the "hybrid" sensor, which features a combination of the "voltage-output type" and "current-output type", was prototyped and evaluated, resulting in a finding of a good development possibility for a sensor that has both the advantages of these two types without impairment to either of them.
引用
收藏
页码:251 / 258
页数:8
相关论文
共 11 条
[1]  
[Anonymous], 1999, TF15330305 CIGRE, P75
[2]  
[Anonymous], 2000, IECStd.60270
[3]   The excitation of UHF signals by partial discharges in GIS [J].
Judd, MD ;
Farish, O ;
Hampton, BF .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1996, 3 (02) :213-228
[4]  
KASI A, 1988, HIGH CONDUCTIVITY SO, P280
[5]  
KOUNO Y, 1989, FLUORIDE ION CONDUCT, V27, P105
[6]  
Lundgaard L. E., 1992, IEEE Electrical Insulation Magazine, V8, P34, DOI 10.1109/57.156943
[7]  
MIURA N, 1987, 4 INT C SOL STAT SEN, V681
[8]  
TAKAHASHI T, 1988, HIGH CONDUCTIVITY SO
[9]   SF6 GAS-ANALYSIS TECHNIQUE AND ITS APPLICATION FOR EVALUATION OF INTERNAL CONDITIONS IN SF6 GAS EQUIPMENT [J].
TOMINAGA, S ;
KUWAHARA, H ;
HIROOKA, K ;
YOSHIOKA, T .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1981, 100 (09) :4196-4206
[10]  
WEPPNER W, 1990, THIN FILM SOLID STAT, P395