Online Monitoring of Power Cables Tangent Delta Based on Low-Frequency Signal Injection Method

被引:23
作者
Zhu, Guangya [1 ]
Zhou, Kai [1 ]
Lu, Lu [2 ]
Li, Yuan [1 ]
Xi, Hang [1 ]
Zeng, Qin [1 ]
机构
[1] Sichuan Univ, Coll Elect & Informat Technol, High Voltage Lab, Chengdu 610065, Peoples R China
[2] Sichuan Univ, Coll Elect & Informat Engn, Chengdu 610065, Peoples R China
基金
中国博士后科学基金; 美国国家科学基金会;
关键词
Interpolating windowed fast Fourier transform (FFT); low-frequency signal injection; online monitoring; power cables; tangent delta (tan delta) measurement;
D O I
10.1109/TIM.2021.3069020
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
To improve the reliability of power systems, online cable condition monitoring must be implemented to replace traditional regular power outage maintenance. Existing online monitoring methods have certain limitations. In this article, a novel method based on low-frequency signal injection is proposed to monitor power cable insulation conditions online. For this method, a low-frequency signal is injected into the power system via the potential transformer (PT) open delta configuration. The cable conductor voltage and leakage current are detected. The interpolating windowed fast Fourier transform (FFT) algorithm is applied to calculate the dielectric loss angle. Then, the cable tangent delta (tan delta) can be deduced, and the cable condition can be assessed. A distribution network system is built based on the power system computer-aided design (PSCAD) software. The frequency and amplitude of the injected signal are simulated and discussed. An online monitoring platform is established in the laboratory. Thermal-aged cable samples and water tree-aged cable samples are prepared and measured. The experimental results confirm that the proposed method can effectively assess power cable insulation.
引用
收藏
页数:8
相关论文
共 20 条
  • [1] [Anonymous], 1999, 619561999 IEC TS
  • [2] [Anonymous], 2009, 60038 IEC
  • [3] [Anonymous], 2012, P4002D12 IEEE, P1
  • [4] Economic Optimization of an Underground Power Cable Installation
    Cichy, Andrzej
    Sakowicz, Bartosz
    Kaminski, Marek
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (03) : 1124 - 1133
  • [5] Online Monitoring and Diagnosis of HV Cable Faults by Sheath System Currents
    Dong, Xiang
    Yang, Yang
    Zhou, Chengke
    Hepburn, Donald M.
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2017, 32 (05) : 2281 - 2290
  • [6] Effects of Temperature on MV Cable Joints Tan Delta Measurements
    Ghaderi, Abbas
    MingottiO, Alessandro
    Lama, Filippo
    Peretto, Lorenzo
    Tinarelli, Roberto
    [J]. IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2019, 68 (10) : 3892 - 3898
  • [7] Effects of Mechanical Pressure on the Tangent Delta of MV Cable Joints
    Ghaderi, Abbas
    Mingotti, Alessandro
    Peretto, Lorenzo
    Tinarelli, Roberto
    [J]. IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2019, 68 (07) : 2656 - 2658
  • [8] HIGH-ACCURACY ANALOG MEASUREMENTS VIA INTERPOLATED FFT
    JAIN, VK
    COLLINS, WL
    DAVIS, DC
    [J]. IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 1979, 28 (02) : 113 - 122
  • [9] Kumazawa T, 1997, PROCEEDINGS OF THE 5TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1 AND 2, P394, DOI 10.1109/ICPADM.1997.617619
  • [10] On-Line Cable Condition Monitoring Using Natural Power Disturbances
    Li, Lulu
    Yong, Jing
    Xu, Wilsun
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2019, 34 (04) : 1242 - 1250