Detection and Location of High Impedance Faults in Multiconductor Overhead Distribution Lines Using Power Line Communication Devices

被引:110
作者
Milioudis, Apostolos N. [1 ]
Andreou, Georgios T. [1 ]
Labridis, Dimitris P. [1 ]
机构
[1] Aristotle Univ Thessaloniki, Dept Elect & Comp Engn, Thessaloniki 54124, Greece
关键词
Fault location; high impedance fault (HIF) detection; multiconductor distribution lines; power distribution faults; power line communications (PLCs); power system protection; smart grids; ENHANCED PROTECTION SCHEME; BROAD-BAND; NEXT-GENERATION; GRIDS; SIMULATION; NETWORK; MODEL;
D O I
10.1109/TSG.2014.2365855
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
An effective power system protection scheme has to be able to detect and locate all occurring faults corresponding to low and high impedance values. The latter category poses the greatest challenge for the protection schemes due to the low values of the related fault current. This paper extends previous work by the authors on the subject, aiming to achieve detection and location of high impedance faults (HIFs) in multiconductor overhead distribution networks utilizing power line communication (PLC) devices. Fault detection is proposed to be performed by a PLC device installed at the starting point of the monitored line and by using differences to the values of metrics related to input impedance at frequencies utilized by narrowband systems. Moreover, fault location can be derived by a response to impulse injection procedure utilized by all installed PLC devices along the line. The method is evaluated and validated in various simulation test cases concerning its ability to effectively detect and locate HIFs.
引用
收藏
页码:894 / 902
页数:9
相关论文
共 42 条
  • [1] Achaichia P, 2013, 2013 17TH IEEE INTERNATIONAL SYMPOSIUM ON POWER LINE COMMUNICATIONS AND ITS APPLICATIONS (ISPLC), P7, DOI 10.1109/ISPLC.2013.6525816
  • [2] Power Line Communications for Low-Voltage Power Grid Tomography
    Ahmed, Mohamed O.
    Lampe, Lutz
    [J]. IEEE TRANSACTIONS ON COMMUNICATIONS, 2013, 61 (12) : 5163 - 5175
  • [3] High-frequency characteristics of overhead multiconductor power lines for broadband communicationsx
    Amirshahi, Pouyan
    Kavehrad, Mohsen
    [J]. IEEE JOURNAL ON SELECTED AREAS IN COMMUNICATIONS, 2006, 24 (07) : 1292 - 1303
  • [4] Broadband power-line communications: The channel capacity analysis
    Anatory, Justinian
    Theethayi, Nelson
    Thottappillil, Rajeev
    Kissaka, Mussa M.
    Mvungi, Nerey H.
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (01) : 164 - 170
  • [5] Medium Voltage Smart Grid: Experimental Analysis of Secondary Substation Narrow Band Power Line Communication
    Artale, Giovanni
    Cataliotti, Antonio
    Cosentino, Valentina
    Di Cara, Dario
    Fiorelli, Riccardo
    Russotto, Pierluca
    Tine, Giovanni
    [J]. IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2013, 62 (09) : 2391 - 2398
  • [6] DISTRIBUTION HIGH IMPEDANCE FAULT-DETECTION UTILIZING HIGH-FREQUENCY CURRENT COMPONENTS
    AUCOIN, BM
    RUSSELL, BD
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (06): : 1596 - 1606
  • [7] Borsche Theodor., 2013, PowerTech (POWERTECH), 2013 IEEE Grenoble, P1
  • [8] Smart Transmission Grid Applications and Their Supporting Infrastructure
    Bose, Anjan
    [J]. IEEE TRANSACTIONS ON SMART GRID, 2010, 1 (01) : 11 - 19
  • [9] Oil-Filled MV/LV Power-Transformer Behavior in Narrow-Band Power-Line Communication Systems
    Cataliotti, Antonio
    Cosentino, Valentina
    Di Cara, Dario
    Tine, Giovanni
    [J]. IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2012, 61 (10) : 2642 - 2652
  • [10] Power-Line Communication in Medium-Voltage System: Simulation Model and Onfield Experimental Tests
    Cataliotti, Antonio
    Di Cara, Dario
    Fiorelli, Riccardo
    Tine, Giovanni
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (01) : 62 - 69