Development and performance of a heat driven R141b ejector air conditioner: Application in hot climate country

被引:25
作者
Thongtip, Tongchana [1 ]
Aphornratana, Satha [2 ]
机构
[1] King Mongkuts Univ Technol North Bangkok, Dept Teacher Training Mech Engn, Bangkok 10800, Thailand
[2] Thammasat Univ, Sirindhorn Int Inst Technol, POB 22,Thammasat Rangsit PO, Pathum Thani 12121, Thailand
关键词
Jet refrigeration; Ejector refrigeration; Air conditioning; Ejector; HCFC-141b; PRIMARY NOZZLE GEOMETRIES; REFRIGERATION SYSTEM; STEAM EJECTOR; CHILLER; DESIGN;
D O I
10.1016/j.energy.2018.07.043
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper proposes the design, construction, and test of a prototype R141b ejector refrigeration system. It was used as an air conditioner for a hot climate country (Thailand). The prototype machine was designed to work as a water chiller to provide thermal comfort condition for the tested room with the cooling capacity up to 4500 W. It was driven by hot water with temperatures of 90-98 degrees C. The condenser was cooled by water, which was provided by a cooling tower, with temperatures of 28-32 degrees C. CFD simulation was also employed to design the ejector. The tested results indicated that the prototype R141b ejector refrigerator working as an air conditioner was satisfactory in operating conditions consistent with a hot climate (Thailand's environment). The temperature of the air conditioned space was around 23 to 25 degrees C with the cooling load of 4500 W. The coefficient of performance (COP) was between 0.42 and 0.47. (C) 2018 Elsevier Ltd. All rights reserved.
引用
收藏
页码:556 / 572
页数:17
相关论文
共 22 条
[1]   A CFD analysis of the flow structure inside a steam ejector to identify the suitable experimental operating conditions for a solar-driven refrigeration system [J].
Allouche, Yosr ;
Bouden, Chiheb ;
Varga, Szabolcs .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2014, 39 :186-195
[2]  
[Anonymous], 2006, FLUENT 6 3 US GUID F
[3]   Computational fluid-dynamics modeling of supersonic ejectors: Screening of turbulence modeling approaches [J].
Besagni, Giorgio ;
Inzoli, Fabio .
APPLIED THERMAL ENGINEERING, 2017, 117 :122-144
[4]   An Integrated Lumped Parameter-CFD approach for off-design ejector performance evaluation [J].
Besagni, Giorgio ;
Mereu, Riccardo ;
Chiesa, Paolo ;
Inzoli, Fabio .
ENERGY CONVERSION AND MANAGEMENT, 2015, 105 :697-715
[5]   Investigation of ejectors in refrigeration system: Optimum performance evaluation and ejector area ratios perspectives [J].
Chen, Jianyong ;
Havtun, Hans ;
Palm, Bjorn .
APPLIED THERMAL ENGINEERING, 2014, 64 (1-2) :182-191
[6]   Turbulence modeling of a single-phase R134a supersonic ejector. Part 1: Numerical benchmark [J].
Croquer, S. ;
Poncet, S. ;
Aidoun, Z. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2016, 61 :140-152
[7]   Results of an experimental study of an advanced jet-pump refrigerator operating with R245fa [J].
Eames, Ian W. ;
Ablwaifa, All E. ;
Petrenko, Volodymyr .
APPLIED THERMAL ENGINEERING, 2007, 27 (17-18) :2833-2840
[8]   The design, manufacture and testing of a jet-pump chiller for air conditioning and industrial application [J].
Eames, Ian W. ;
Milazzo, Adriano ;
Paganini, Dario ;
Livi, Michele .
APPLIED THERMAL ENGINEERING, 2013, 58 (1-2) :234-240
[9]   A THEORETICAL AND EXPERIMENTAL-STUDY OF A SMALL-SCALE STEAM JET REFRIGERATOR [J].
EAMES, IW ;
APHORNRATANA, S ;
HAIDER, H .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1995, 18 (06) :378-386
[10]   An experimental and computational study of the flow pattern in a refrigerant ejector. Validation of turbulence models and real-gas effects [J].
Garcia del Valle, J. ;
Sierra-Pallares, J. ;
Garcia Carrascal, P. ;
Castro Ruiz, F. .
APPLIED THERMAL ENGINEERING, 2015, 89 :795-811