Performance analysis of a multistage internal circulation liquid desiccant dehumidifier

被引:18
作者
Cheng, Xingwang [1 ]
Rong, Yangyiming [1 ]
Zhou, Xia [1 ]
Gu, Chenjie [1 ]
Zhi, Xiaoqin [1 ]
Qiu, Limin [1 ]
Yuan, Yijun [2 ]
Wang, Kai [1 ]
机构
[1] Zhejiang Univ, Inst Refrigerat & Cryogen, Hangzhou 310027, Peoples R China
[2] Hangzhou Xinghuan Co Ltd, Hangzhou 311200, Peoples R China
基金
国家重点研发计划;
关键词
Liquid desiccant dehumidifier; Multistage; Internal circulation; Theoretical analysis; MASS-TRANSFER COEFFICIENTS; AIR-CONDITIONING SYSTEM; COOLED/HEATED DEHUMIDIFIER/REGENERATOR; HEAT; COUNTER; MODEL;
D O I
10.1016/j.applthermaleng.2020.115163
中图分类号
O414.1 [热力学];
学科分类号
摘要
A novel multistage internal circulation liquid desiccant dehumidifier (MICLDD) is proposed for feed air drying of air compressors in a cryogenic air separation unit (ASU). The dehumidifier is designed in a multistage structure, in which the packing bed and cooling module are layered separately inside each stage. The solution concentration and flow rate can be evenly distributed according to the moisture content distribution along the dehumidification process using the internal circulation structure. A numerical model validated by using experimental data from previous literatures, is employed to simulate the heat and mass transfer process within the dehumidifier. Effects of the inlet parameters and the number of packing stages on the dehumidification performance are investigated. Results show that the dehumidification efficiency is mainly affected by the mass flow rate of desiccant solution and increases with the mass flow rate of desiccant solution. With the increase of packing series, the heat and mass transfer area increases proportionally, so the dehumidification efficiency is improved. Compared to the structure of the packed tower with cooling tubes proposed in Ref. 1121, the dehumidification efficiency of the MICLDD can be improved by 7.3% with the same pump power consumption.
引用
收藏
页数:10
相关论文
共 27 条
[1]   Evaluation of heat and mass transfer coefficients in a gauze-type structured packing air dehumidifier operating with liquid desiccant [J].
Al-Farayedhi, AA ;
Gandhidasan, P ;
Al-Mutairi, MA .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2002, 25 (03) :330-339
[2]   Performance comparison of an adiabatic and an internally cooled structured packed-bed dehumidifier [J].
Bansal, Pradeep ;
Jain, Sanjeev ;
Moon, Choon .
APPLIED THERMAL ENGINEERING, 2011, 31 (01) :14-19
[3]   Performance analysis of a hybrid air-conditioning system dehumidified by liquid desiccant with low temperature and low concentration [J].
Chen, Yao ;
Yin, Yonggao ;
Zhang, Xiaosong .
ENERGY AND BUILDINGS, 2014, 77 :91-102
[4]   Experimental analysis of dehumidification performance of counter and cross-flow liquid desiccant dehumidifiers [J].
Cho, Hye-Jin ;
Cheon, Seong-Yong ;
Jeong, Jae-Weon .
APPLIED THERMAL ENGINEERING, 2019, 150 :210-223
[5]   CORRELATING EQUATION FOR FORCED-CONVECTION FROM GASES AND LIQUIDS TO A CIRCULAR-CYLINDER IN CROSS-FLOW [J].
CHURCHILL, SW ;
BERNSTEIN, M .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1977, 99 (02) :300-306
[6]   Properties of aqueous solutions of lithium and calcium chlorides: formulations for use in air conditioning equipment design [J].
Conde, MR .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2004, 43 (04) :367-382
[7]  
GNIELINSKI V, 1976, INT CHEM ENG, V16, P359
[8]   Energy saving opportunities in air drying process in high-pressure compressors [J].
Goodarzia, Gholamreza ;
Dehghani, Saeed ;
Akbarzadeh, Aliakbar ;
Date, Abhijit .
1ST INTERNATIONAL CONFERENCE ON ENERGY AND POWER, ICEP2016, 2017, 110 :428-433
[9]   Energy Impact of Air Pre-cooling on Screw Air Compressor [J].
Guo, Da ;
Ma, Zhixian ;
Zhang, Jili ;
Liu, Mingsheng .
10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 :937-944
[10]   Studying the heat and mass transfer process of liquid desiccant for dehumidification and cooling [J].
Islam, M. R. ;
Alan, S. W. L. ;
Chua, K. J. .
APPLIED ENERGY, 2018, 221 :334-347