A comprehensive experimental approach for the validation of quantitative infrared thermography in the evaluation of building thermal transmittance

被引:129
作者
Albatici, Rossano [1 ]
Tonelli, Arnaldo M.
Chiogna, Michela [2 ]
机构
[1] Univ Trent, Dept Civil Environm & Mech Engn, I-38123 Trento, Italy
[2] Ist Trentino Edilizia Abitat SpA, I-38121 Trento, Italy
关键词
Infrared thermovision technique; Quantitative thermography; Thermal transmittance; On site monitoring; Energy performance; TEMPERATURE; COEFFICIENT; PARAMETERS; ENVELOPE; SURFACE;
D O I
10.1016/j.apenergy.2014.12.035
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Quantitative thermography is now mostly accepted as a reliable method to measure energy performance of existing buildings, in particular the thermal transmittance U-values of opaque elements. Some researches have been conducted in this field, each presenting a different procedure verified by the application on simple case studies. Anyway, a comprehensive approach, based on a parametric analysis of walls with different typologies and exposure, but same boundary conditions, is still missing. This study proposes a systematic approach to the problem, based on a three years research activity carried on an experimental building where timber (light) and brick (heavy) structures were tested simultaneously with Infrared Thermovision Technique (ITT), also equipped with heat flow meter (HFM) sensors and a nearby meteo station. Standard deviation of U-values measured with ITT is given as well as absolute deviation against values calculated following international standards and measured with HFM method. Parameters having high significance for the achievement of good results compared to the expected U-values are assessed through a sensitivity analysis. Influence of weather conditions during the survey are also considered and a repeatable procedure is finally set up. The findings presented in the study show that the method gives good results for heavy constructions, while further studies are still needed for light and super-insulated walls. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:218 / 228
页数:11
相关论文
共 25 条
  • [1] Assessment of the thermal emissivity value of building materials using an infrared thermovision technique emissometer
    Albatici, Rossano
    Passerini, Francesco
    Tonelli, Arnaldo M.
    Gialanella, Stefano
    [J]. ENERGY AND BUILDINGS, 2013, 66 : 33 - 40
  • [2] Infrared thermovision technique for the assessment of thermal transmittance value of opaque building elements on site
    Albatici, Rossano
    Tonelli, Arnaldo M.
    [J]. ENERGY AND BUILDINGS, 2010, 42 (11) : 2177 - 2183
  • [3] [Anonymous], 1994, 10351 UNI
  • [4] [Anonymous], 2008, 15603 UNI EN
  • [5] [Anonymous], 1994, 9869 ISO
  • [6] [Anonymous], 2009, USER MANUAL FLIR REP, VT559081
  • [7] [Anonymous], 2008, 13786 UNI EN ISO
  • [8] [Anonymous], 2000, 13187 UNI EN ISO
  • [9] [Anonymous], 2008, UNI EN ISO 6946
  • [10] A quantitative methodology to evaluate thermal bridges in buildings
    Asdrubali, Francesco
    Baldinelli, Giorgio
    Bianchi, Francesco
    [J]. APPLIED ENERGY, 2012, 97 : 365 - 373