Mechanical-condition Assessment of Power Transformer Using Vibroacoustic Analysis

被引:8
作者
Kornatowski, Eugeniusz [1 ]
机构
[1] W Pomeranian Uniwers Technol, PL-71126 Szczecin, Poland
来源
ADVANCED MATERIALS IN MICROWAVES AND OPTICS | 2012年 / 500卷
关键词
Transformer; vibration characteristic; diagnostic;
D O I
10.4028/www.scientific.net/KEM.500.40
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This paper presents a method for vibroacoustic analysis of a transformer in the steady state. The standard approach to this problem has been based on analysis of the vibration frequency spectrum recorded with an accelerometer mounted on the transformer's tank. To improve legibility of measurement results, the paper suggests the analysis method for the relative coefficient of harmonic frequency contents h(norm)(f). The conducted experiment showed that high values of h(norm) within a wide frequency range testify to deformation of windings and degradation of solid insulation.
引用
收藏
页码:40 / 44
页数:5
相关论文
共 13 条
  • [1] Antipov G. V., 1996, MEASUREMENTS TECHNOL, V39
  • [2] Banaszak Sz., 2008, PRZEGLAD ELEKTROTECH
  • [3] Barbare A., 1993, CIGRE S BERL
  • [4] Vibro-acoustic techniques to diagnose power transformers
    Bartoletti, C
    Desiderio, M
    Di Carlo, D
    Fazio, G
    Muzi, F
    Sacerdoti, G
    Salvatori, F
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (01) : 221 - 229
  • [5] Berler Z., 2000, 2000 IEEE INT S EL I
  • [6] Birlasekaran S., 1999, IEEE POWER ENG REV, V19
  • [7] Borucici S., 2010, PRZEGLAD ELEKTROTECH
  • [8] Both C., 1995, AM POW C
  • [9] CIGRE Working Group A2. 26, 2008, A226 CIGRE WORK GROU, V342
  • [10] Dobrucki A., 2007, Przetworniki Elektroakustyczne