Assessing electrical bottlenecks at feeder level for residential net zero-energy buildings by integrated system simulation

被引:164
作者
Baetens, R. [1 ]
De Coninck, R. [2 ,4 ]
Van Roy, J. [3 ]
Verbruggen, B. [3 ]
Driesen, J. [3 ]
Helsen, L. [2 ]
Saelens, D. [1 ]
机构
[1] KU Leuven Leuven Univ, Dept Civil Engn, Bldg Phys Sect, Louvain, Belgium
[2] KU Leuven Leuven Univ, Dept Mech Engn, Appl Mech & Energy Convers Sect, Louvain, Belgium
[3] KU Leuven Leuven Univ, Dept Elect Engn, Louvain, Belgium
[4] 3E, Brussels, Belgium
基金
比利时弗兰德研究基金会;
关键词
Zero energy building; Residential; Thermal demand; Electricity demand; Dynamic simulation; District; MODEL; GENERATION; VALIDATION; OCCUPANCY; SURFACES;
D O I
10.1016/j.apenergy.2011.12.098
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Recent European communications focus on the enforcement that by 2020 all new buildings are nearly Zero-Energy Buildings (ZEBs) and on the deployment of a European Smart Grid. The presented work focuses on assessing the electrical challenges at neighborhood level of an building stock evolving towards ZEBs, and identifying the resulting challenge in multidisciplinary dynamic simulation models required to perform this assessment. A tool for Integrated District Energy Assessment by Simulation (IDEAS) is developed. This IDEAS tool allows simultaneous transient simulation of thermal and electrical systems at both building and feeder level. Residential ZEBs show a self-consumption of locally generated photovoltaic (PV) electricity of 26 +/- 4% at building level. Resulting feeder voltage fluctuations and possible transformer overload are quantified as bottlenecks. When all dwellings are intended to achieve a ZEB status, (i) a fraction of 14-47% of local PV supply is wasted by inverter curtailing depending on the feeder strength, while (ii) the peak transformer load is found to be 3.3 kVA per dwelling which may affect power security in existing feeder designs. (C) 2012 Elsevier Ltd. All rights reserved.
引用
收藏
页码:74 / 83
页数:10
相关论文
共 69 条
[61]  
Vanneste D, 2001, SOCIAAL EC ENQUETE 2
[62]  
Verbeeck G, 2007, THESIS KU LEUVEN
[63]   Modeling occupancy in single person offices [J].
Wang, D ;
Federspiel, CC ;
Rubinstein, F .
ENERGY AND BUILDINGS, 2005, 37 (02) :121-126
[64]   Impacts of different data averaging times on statistical analysis of distributed domestic photovoltaic systems [J].
Widen, Joakim ;
Wackelgard, Ewa ;
Paatero, Jukka ;
Lund, Peter .
SOLAR ENERGY, 2010, 84 (03) :492-500
[65]   A combined Markov-chain and bottom-up approach to modelling of domestic lighting demand [J].
Widen, Joakim ;
Nilsson, Annica M. ;
Wackelgard, Ewa .
ENERGY AND BUILDINGS, 2009, 41 (10) :1001-1012
[66]   The nature of domestic electricity-loads and effects of time averaging on statistics and on-site generation calculations [J].
Wright, Andrew ;
Firth, Steven .
APPLIED ENERGY, 2007, 84 (04) :389-403
[67]   Proposal of a modeling approach considering urban form for evaluation of city level energy management [J].
Yamaguchi, Y. ;
Shimoda, Y. ;
Mizuno, M. .
ENERGY AND BUILDINGS, 2007, 39 (05) :580-592
[68]   District-scale simulation for multi-purpose evaluation of urban energy systems [J].
Yamaguchi, Yohei ;
Shimoda, Yoshiyuki .
JOURNAL OF BUILDING PERFORMANCE SIMULATION, 2010, 3 (04) :289-305
[69]   Implications of urban settings for the design of photovoltaic and conventional facades [J].
Yun, Geun Young ;
Steemers, Koen .
SOLAR ENERGY, 2009, 83 (01) :69-80