Using the three-parameter Weibull distribution in assessment of threshold strength of pressboard impregnated by different liquid dielectrics

被引:21
作者
Rozga, Pawel [1 ]
机构
[1] Lodz Univ Technol, Inst Elect Power Engn, Stefanowskiego 18-22, PL-90924 Lodz, Poland
关键词
electric strength; dielectric liquids; Weibull distribution; statistical analysis; minerals; voltage measurement; electric breakdown; oils; size; 0; 5; mm; 1; three-parameter Weibull distribution; liquid dielectrics; pressboard impregnated specimen; electrical strength measurement; mineral oil; natural ester; synthetic ester; IEC; 60243; standard; breakdown voltage; statistical approach; MINERAL-OIL; ELECTRICAL STRENGTH; POWER TRANSFORMERS; NATURAL ESTER; INSULATION; BREAKDOWN; VOLTAGE; PAPER;
D O I
10.1049/iet-smt.2016.0061
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This study presents the results of the measurements of electrical strength of pressboard specimens impregnated with three different liquid dielectrics: mineral oil, natural ester and synthetic ester. In the experiment carried out in accordance with IEC 60243 standard, two types of pressboard specimens of thicknesses 0.5 and 1 mm, respectively, were considered. The data obtained during the measurements in the form of breakdown voltages were used for calculation of the electrical strength. Both standard-based approach where median value was taken into account in calculations and statistical approach using three-parameter Weibull distribution function where location parameter V-0 was considered were applied. The results obtained on the basis of both approaches showed that both the specimens impregnated with mineral oil and ester liquids gave the satisfactory results within the electrical strength determined, which in all cases was higher than minimum required for the impregnated pressboards. The differences indicating slightly better impregnation properties of mineral oil, when the same impregnation conditions are used, are noticeable especially in the case of location parameter of Weibull distribution function. However, these differences are small and in relation to the requirements for the impregnated pressboards may be treated as negligible.
引用
收藏
页码:665 / 670
页数:6
相关论文
共 22 条
[1]   METHOD OF MAXIMUM LIKELIHOOD APPLIED TO ANALYSIS OF FLASHOVER DATA [J].
BROWN, GW .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1969, PA88 (12) :1823-&
[2]   SIMULTANEOUS ESTIMATION OF LOCATION AND SCALE PARAMETERS OF WEIBULL DISTRIBUTION [J].
CHAN, LK ;
CHENG, SW ;
MEAD, ER .
IEEE TRANSACTIONS ON RELIABILITY, 1974, R 23 (05) :335-341
[3]   Life-Data Analysis for Condition Assessment of High-Voltage Assets [J].
Chmura, Lukasz ;
Morshuis, Peter H. F. ;
Smit, Johan J. ;
Janssen, Anton .
IEEE ELECTRICAL INSULATION MAGAZINE, 2015, 31 (05) :33-43
[4]   Aging Behavior of Cellulosic Materials in Presence of Mineral Oil and Ester Liquids under Various Conditions [J].
Coulibaly, M-L. ;
Perrier, C. ;
Marugan, M. ;
Beroual, A. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2013, 20 (06) :1971-1976
[5]  
Cousineau D, 2002, IEEE T DIELECT EL IN, V9, P524, DOI [10.1109/TDEI.2002.1024429, DOI 10.1109/TDEI.2002.1024429]
[6]   A comparison of the impregnation of cellulose insulation by ester and mineral oil [J].
Dai, J. ;
Wang, Z. D. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2008, 15 (02) :374-381
[7]   Comparative evaluation of alternative fluids for power transformers [J].
Fernandez, Inmaculada ;
Ortiz, Alfredo ;
Delgado, Fernando ;
Renedo, Carlos ;
Perez, Severiano .
ELECTRIC POWER SYSTEMS RESEARCH, 2013, 98 :58-69
[8]   Electrical strength of pressboard components for transformer insulations [J].
Giese, K .
IEEE ELECTRICAL INSULATION MAGAZINE, 1996, 12 (01) :29-33
[9]   Influence of natural ester on frequency dielectric response of impregnated insulation pressboard [J].
Hao, J. ;
Liao, R. ;
Ma, Z. ;
Yang, L. .
IET SCIENCE MEASUREMENT & TECHNOLOGY, 2012, 6 (06) :403-411
[10]   Maximum likelihood parameter estimation in the extended Weibull distribution and its applications to breakdown voltage estimation [J].
Hirose, H .