Comparative Analysis of Heat Pump System with IHX Using R1234yf and R134a

被引:4
作者
Santa, Robert [1 ]
机构
[1] Univ Dunaujvaros, Dept Mech Engn, Tancsics Mihaly U 1-a, H-2400 Dunaujvaros, Hungary
来源
PERIODICA POLYTECHNICA-MECHANICAL ENGINEERING | 2021年 / 65卷 / 04期
关键词
heat pump; IHX; R1234yf; R134a; COP; DROP-IN REPLACEMENT; EXERGY ANALYSIS; PERFORMANCE; EXCHANGER; R513A; R450A; ALTERNATIVES; MIXTURE; R1234ZE(E); ENERGY;
D O I
10.3311/PPme.18390
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
This research presents an energy performance analysis of the heat pump system with internal heat exchanger (IHX). The mathematical model of the heat pump outlined in this paper has been created by the author, it is steady-state with lumped parameters. The experimental validation of the model has been carried out using R1234yf and R134a as refrigerant. The aim of this work is to compare the energy performance in a wide range of operating conditions of a monitored heat pump system using both refrigerants. Finally, the heating capacity for R1234yf was lower from 0.63 % to 7.54 % compared with R134a, while the compressor power was similar from 0.12 % to 3.51 %. The COP values of R1234yf were lower than those obtained of R134a, ranging from 1.39 % to 4.22 %.
引用
收藏
页码:363 / 373
页数:11
相关论文
共 31 条
  • [1] Experimental study of R1234yf as a drop-in replacement for R134a in a domestic refrigerator
    Belman-Flores, J. M.
    Rodriguez-Munoz, A. P.
    Gutierrez Perez-Reguera, C.
    Mota-Babiloni, A.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2017, 81 : 1 - 11
  • [2] Energy and exergy analysis of R1234yf as drop-in replacement for R134a in a domestic refrigeration system
    Belman-Flores, J. M.
    Rangel-Hernandez, V. H.
    Uson, S.
    Rubio-Maya, C.
    [J]. ENERGY, 2017, 132 : 116 - 125
  • [3] Experimental investigation on the influence of internal heat exchanger in a transcritical CO2 heat pump water heater
    Cao, Feng
    Ye, Zuliang
    Wang, Yikai
    [J]. APPLIED THERMAL ENGINEERING, 2020, 168 (168)
  • [4] Theoretical analysis of internal heat exchanger in transcritical CO2 heat pump systems and its experimental verification
    Cao, Feng
    Wang, Yikai
    Ye, Zuliang
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 106 : 506 - 516
  • [5] Performance characteristics of an automobile air conditioning system with internal heat exchanger using refrigerant R1234yf
    Cho, Honghyun
    Lee, Hoseong
    Park, Chasik
    [J]. APPLIED THERMAL ENGINEERING, 2013, 61 (02) : 563 - 569
  • [6] A comparative study on the performance of HFO-1234yf and HFC-134a as an alternative in automotive air conditioning systems
    Daviran, Samaneh
    Kasaeian, Alibakhsh
    Golzari, Soudabeh
    Mahian, Omid
    Nasirivatan, Shahin
    Wongwises, Somchai
    [J]. APPLIED THERMAL ENGINEERING, 2017, 110 : 1091 - 1100
  • [7] Improvement on the energy performance of a refrigeration system adapting a plate-type heat exchanger and low-GWP refrigerants as alternatives to R134a
    Devecioglu, Atilla G.
    Oruc, Vedat
    [J]. ENERGY, 2018, 155 : 105 - 116
  • [9] Duarte MV, 2017, OPEN ENG, V7, P77, DOI 10.1515/eng-2017-0011
  • [10] Modelling thermostatic expansion valves
    Eames, Ian W.
    Milazzo, Adriano
    Maidment, Graeme G.