Localization of Partial Discharge in Transformer Oil Using Fabry-Perot Optical Fiber Sensor Array

被引:46
作者
Gao, Chaofei [1 ]
Wang, Wei [1 ]
Song, Shu [1 ]
Wang, Shijie [1 ]
Yu, Lei [1 ]
Wang, Yangchao [1 ]
机构
[1] North China Elect Power Univ, Beijing Key Lab High Voltage & Electromagnet Comp, State Key Lab Alternate Elect Power Syst Renewabl, Beijing 102206, Peoples R China
基金
中国国家自然科学基金;
关键词
ultrasonic signals of partial discharge; Fabry-Perot fiber-optic sensor array; steered response power algorithm; partial discharge localization; POWER TRANSFORMERS; ACOUSTIC DETECTION; SOURCE LOCATION; PD DETECTION; IDENTIFICATION; OPTIMIZATION; SYSTEM;
D O I
10.1109/TDEI.2018.007065
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Partial discharge is the main reason for insulation deterioration and failure of high voltage electrical asset. Thus, the online detection and localization of partial discharge can provide the information on the equipment degradation characteristics, and moreover, is of great value for improving the safe operation of the power grid and the developing of optimal maintenance. Accounting for the good sensitivity, the high immunity to electromagnetic interference, the compact size with outstanding insulation level, the Fabry-Perot optical fiber sensor is attracting increasing attention as a promising way for online acoustic partial discharge localization. In this study, the partial discharge localization in the transformer oil is realized by an ultrasonic detection system, which is consisting of 2x2 Fabry-Perot optical fiber sensor array with steered response power algorithm. In general, the Fabry-Perot optical fiber acoustic sensor array shows good direction sharpness, and achieves accurate localization. This detection and localization system is further applied to a 35 kV transformer single-phase winding and verified with partial discharges on the outer winding.
引用
收藏
页码:2279 / 2286
页数:8
相关论文
共 28 条
[1]   Autonomous Localization of Partial Discharge Sources within Large Transformer Windings [J].
Abd Rahman, M. S. ;
Lewin, P. L. ;
Rapisarda, P. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (02) :1088-1098
[2]   Transfer function-based partial discharge localization in power transformers: A feasibility study [J].
Akbari, A ;
Werle, P ;
Borsi, H ;
Gockenbach, E .
IEEE ELECTRICAL INSULATION MAGAZINE, 2002, 18 (05) :22-32
[3]   Partial Discharge Detection Using Acoustic and Optical Methods in High Voltage Power Equipments: A Review [J].
Al Saedi, Malik Abdul Razzaq ;
Yaacob, Mohd Muhridza .
MATERIALS, INDUSTRIAL, AND MANUFACTURING ENGINEERING RESEARCH ADVANCES 1.1, 2014, 845 :283-286
[4]   A Novel Bias Detection Technique for Partial Discharge Localization in Oil Insulation System [J].
Al-Masri, Wasim M. F. ;
Abdel-Hafez, Mamoun F. ;
El-Hag, Ayman H. .
IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2016, 65 (02) :448-457
[5]   A Methodology for Identification and Localization of Partial Discharge Sources using Optical Sensors [J].
Biswas, S. ;
Koley, C. ;
Chatterjee, B. ;
Chakravorti, S. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2012, 19 (01) :18-28
[6]   Instrumentation System for Location of Partial Discharges Using Acoustic Detection With Piezoelectric Transducers and Optical Fiber Sensors [J].
Bua-Nunez, Iago ;
Posada-Roman, Julio E. ;
Rubio-Serrano, Jesus ;
Garcia-Souto, Jose A. .
IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2014, 63 (05) :1002-1013
[7]   A Time-domain Characterization Method for UHF Partial Discharge Sensors [J].
Chen, Xiaoxin ;
Qian, Yong ;
Sheng, Gehao ;
Jiang, Xiuchen .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (01) :110-119
[8]   Location of PD Sources in Power Transformers by UHF and Acoustic Measurements [J].
Coenen, Sebastian ;
Tenbohlen, Stefan .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2012, 19 (06) :1934-1940
[9]  
DO H., 2009, REAL TIME SRP PHAT S
[10]  
Do H, 2007, INT CONF ACOUST SPEE, P121