Experimental investigations of pump-driven closed-loop thermosyphon system

被引:5
作者
Birajdar, Mahasidha R. [1 ,2 ]
Sewatkar, Chandrasekhar M. [3 ]
机构
[1] Coll Engn Pune, Dept Mech Engn, Pune 411005, Maharashtra, India
[2] Trinity Coll Engn & Res, Dept Mech Engn, Pune, Maharashtra, India
[3] Govt Coll Engn & Res, Dept Mech Engn, Pune, Maharashtra, India
关键词
adiabatic length; pump-driven closed-loop thermosyphon; thermal resistance; water and geyser boiling; HEAT-PIPE SYSTEM; COOLING SYSTEM; 2-PHASE; PERFORMANCE; INSTABILITY;
D O I
10.1002/htj.22649
中图分类号
O414.1 [热力学];
学科分类号
摘要
The thermal management of the compact electronic system is one of the major challenges in the present power electronics and computational industries. The present paper investigates the effects of a pump-driven flow on the thermal performance of a closed-loop thermosyphon (CLT) system. This paper discusses the effect of pump-driven flow on the thermal performance of CLT. In this study, the experimentation is carried out on the water-charged pump-driven closed-loop thermosyphon (PDLT) with different heat inputs, filling ratios (FR), and adiabatic lengths to understand the effects of these parameters on the thermal performance of the system. The results indicate that the heat transfer performance of CLT is improved using pump-driven flow in the PDLT and the minimum thermal resistance (0.035 k/W) is obtained at FR = 0.6 and 3 kW heat input. It is also noticed that the thermal resistance of PDLT is up to 35% higher than CLT at FR = 0.6, 0.5 kW heat input, and 500 mm adiabatic length. The unstable geyser boiling phenomenon is eliminated from the system at the adiabatic lengths of 200 and 500 mm. However, for long adiabatic length (800 mm), the geyser boiling occurs at a higher FR (FR = 0.6) and moderate heat flux (0.5 kW).
引用
收藏
页码:7387 / 7410
页数:24
相关论文
共 33 条
[1]  
Birajdar Mahasidha R., 2020, Advances in Applied Mechanical Engineering. Select Proceedings of ICAMER 2019. Lecture Notes in Mechanical Engineering (LNME), P37, DOI 10.1007/978-981-15-1201-8_5
[2]   Effect of adiabatic length on the performance of closed-loop thermosyphon system [J].
Birajdar, Mahasidha R. ;
Sewatkar, Chandrasekhar M. .
HEAT TRANSFER, 2020, 49 (08) :4448-4474
[3]   A review on independent and integrated/coupled two-phase loop thermosyphons [J].
Cao, Jingyu ;
Zheng, Zhanying ;
Asim, Muhammad ;
Hu, Mingke ;
Wang, Qiliang ;
Su, Yuehong ;
Pei, Gang ;
Leung, Michael K. H. .
APPLIED ENERGY, 2020, 280
[4]   Performance characteristics of variable conductance loop thermosyphon for energy-efficient building thermal control [J].
Cao, Jingyu ;
Hong, Xiaoqiang ;
Zheng, Zhanying ;
Asim, Muhammad ;
Hu, Mingke ;
Wang, Qiliang ;
Pei, Gang ;
Leung, Michael K. H. .
APPLIED ENERGY, 2020, 275
[5]   Experimental evaluation of the thermal performances of a thermosyphon cooling system rejecting heat by natural and forced convection [J].
Cataldo, Filippo ;
Thome, John R. .
APPLIED THERMAL ENGINEERING, 2017, 127 :1404-1415
[6]   Sub-atmospheric boiling heat transfer and thermal performance of two-phase loop thermosyphon [J].
Chang, S. W. ;
Lo, D. C. ;
Chiang, K. F. ;
Lin, C. Y. .
EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2012, 39 :134-147
[7]   Experimental investigation of geyser boiling in a small diameter two-phase loop thermosyphon [J].
Elkholy, A. ;
Kempers, R. .
EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2020, 118
[8]  
Faghri Amir., 1995, HEAT PIPE SCI TECHNO
[9]   Experimental analysis of Closed Loop Two Phase Thermosyphon (CLTPT) for energy systems [J].
Franco, Alessandro ;
Filippeschi, Sauro .
EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2013, 51 :302-311
[10]   Closed Loop Two-Phase Thermosyphon of Small Dimensions: a Review of the Experimental Results [J].
Franco, Alessandro ;
Filippeschi, Sauro .
MICROGRAVITY SCIENCE AND TECHNOLOGY, 2012, 24 (03) :165-179