Line-Interactive Single-Phase Dynamic Voltage Restorer With Novel Sag Detection Algorithm

被引:45
作者
Bae, B. [1 ]
Lee, J. [2 ]
Jeong, J. [2 ]
Han, B. [2 ]
机构
[1] LS Ind Syst Co Ltd, Res Engn HVDC Res Team R&D Ctr, Anyang 431080, South Korea
[2] Myongji Univ, Dept Elect Engn, Myongji 449728, South Korea
关键词
Discrete Fourier transform (DFT); dynamic voltage restorer (DVR); line-interactive; phase-locked loop (PLL); root mean square (rms) variation detector; voltage sag or interruption; DVR; LEVEL;
D O I
10.1109/TPWRD.2010.2044194
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper describes the development of a line-interactive single-phase dynamic voltage restorer (DVR) with a novel sag detection algorithm. The developed detection algorithm has a hybrid structure composed of an instantaneous detection part and the root-mean-square (rms) variation detection part. The source voltage passes through the instantaneous sag detection part. If instantaneous sag is detected, the rms variation detector-1 is selected to calculate the rms variation. The rms variation detector-2 is selected when the instantaneous sag occurs under the operation of the rms variation detector-1. The feasibility of proposed algorithm was verified through computer simulations and experimental works with a 3-kVA-rating prototype of line-interactive DVR. The line-interactive DVR with the proposed algorithm can compensate the input voltage sag or interruption within 2.0-ms delay. The developed DVR can be effectively utilized for the sensitive loads, such as a computer, communication device, and automation device.
引用
收藏
页码:2702 / 2709
页数:8
相关论文
共 9 条
[1]   Voltage sag detection technique for a dynamic voltage restorer [J].
Fitzer, C ;
Barnes, M ;
Green, P .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2004, 40 (01) :203-212
[2]   Voltage sag detection based on rectified voltage processing [J].
Florio, A ;
Mariscotti, A ;
Mazzucchelli, M .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (04) :1962-1967
[3]   Novel phase-locked loop using adaptive linear combiner [J].
Han, B ;
Bae, B .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (01) :513-514
[4]   Combined operation of unified power-quality conditioner with distributed generation [J].
Han, B ;
Bae, B ;
Kim, H ;
Baek, S .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (01) :330-338
[5]   Optimized Control Strategy for a Medium-Voltage DVR-Theoretical Investigations and Experimental Results [J].
Meyer, Christoph ;
De Doncker, Rik W. ;
Li, Yun Wei ;
Blaabjerg, Frede .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2008, 23 (06) :2746-2754
[6]   A new method of voltage sag and swell detection [J].
Naidoo, Raj ;
Pillay, Pragasen .
IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (02) :1056-1063
[7]   A dynamic voltage restorer (DVR) with selective harmonic compensation at medium voltage level [J].
Newman, MJ ;
Holmes, DG ;
Nielsen, JG ;
Blaabjerg, F .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2005, 41 (06) :1744-1753
[8]   Control and testing of a dynamic voltage restorer (DVR) at medium voltage level [J].
Nielsen, JG ;
Newman, M ;
Nielsen, H ;
Blaabjerg, F .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2004, 19 (03) :806-813
[9]   Dynamic voltage restorer based on voltage-space-vector PWM control [J].
Zhan, CJ ;
Ramachandaramurthy, VK ;
Arulampalam, A ;
Fitzer, C ;
Kromlidis, S ;
Barnes, M ;
Jenkins, N .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2001, 37 (06) :1855-1863