An experimental study on liquid regeneration process of a liquid desiccant air conditioning system (LDACs) based on vacuum membrane distillation

被引:33
作者
Zhou, Junming [1 ,2 ]
Wang, Faming [2 ,3 ]
Noor, Nuruzzaman [2 ]
Zhang, Xiaosong [1 ]
机构
[1] Southeast Univ, Sch Energy & Environm, Nanjing, Peoples R China
[2] Hong Kong Polytech Univ, Inst Text & Clothing, Mat Synth & Proc Lab, Hung Hom,Kowloon, Hong Kong, Peoples R China
[3] Cent South Univ, Sch Architecture & Art, Changsha, Peoples R China
基金
中国国家自然科学基金;
关键词
Liquid dehumidification; Experiment; VMD; Regeneration ability; SEAWATER DESALINATION; PERFORMANCE ANALYSIS; SIMULATION;
D O I
10.1016/j.energy.2019.116891
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this paper, a liquid regeneration method by vacuum membrane distillation (VMD) is proposed for the liquid desiccant air conditioning system (LDAC5), and the experimental study on this method is carried out. VMD regeneration experiments were carried out with LiCl solution. The effects of temperature, concentration of feed solution, length, number of fiber membranes and vacuum pressure on the membrane flux, mass transfer coefficient, rejection rate and regeneration ability were studied. The results show that the error between experimental and calculation results is reduced from less than 15% to less than 5% by the optimized calculation model. The temperature of feed solution has a great influence on the regeneration performance of VMD, and the regeneration ability of VMD process increases approximately exponentially from about 0.1% to 0.8-1.2% with the increase of regeneration temperature. The VMD regeneration process of LiCl solution is the result of Poiseuille flow and Knudsen diffusion, and Poiseuille flow dominates. Under the same regeneration capacity, the regeneration temperature of 30 wt % LiCl solution is about 7 degrees C higher than that of 20 wt% LiCl solution, and this temperature difference also increases as the target regeneration amount increases. In order to improve the regeneration effect of high concentration solution, the regeneration temperature can be increased appropriately. The water flux of the membrane decreases with the increase of the length of the membrane. The membrane length of Typel is 2.1 times longer than Type 2, but regeneration capacity of Type 1 is only 1-1.7 times higher than Type 2. Further, both the water flux and regeneration ability of the solution decrease first and then increase with the increasing number of membranes. Therefore, the reasonable selection of number of fiber membranes can significantly save materials and also improve the regeneration ability. (C) 2020 Elsevier Ltd. All rights reserved.
引用
收藏
页数:9
相关论文
共 29 条
[1]   A comprehensive review of vacuum membrane distillation technique [J].
Abu-Zeid, Mostafa Abd El-Rady ;
Zhang, Yaqin ;
Dong, Hang ;
Zhang, Lin ;
Chen, Huan-Lin ;
Hou, Lian .
DESALINATION, 2015, 356 :1-14
[2]   Potential of membrane distillation in seawater desalination: Thermal efficiency, sensitivity study and cost estimation [J].
Al-Obaidani, Sulaiman ;
Curcio, Efrem ;
Macedonio, Francesca ;
Di Profio, Gianluca ;
Ai-Hinai, Hilal ;
Drioli, Enrico .
JOURNAL OF MEMBRANE SCIENCE, 2008, 323 (01) :85-98
[3]   Membrane distillation: A comprehensive review [J].
Alkhudhiri, Abdullah ;
Darwish, Naif ;
Hilal, Nidal .
DESALINATION, 2012, 287 :2-18
[4]   Performance of vacuum poly(propylene) membrane distillation (VMD) for saline water desalination [J].
Alsalhy, Qusay F. ;
Ibrahim, Salah S. ;
Khaleel, Samraa R. .
CHEMICAL ENGINEERING AND PROCESSING-PROCESS INTENSIFICATION, 2017, 120 :68-80
[5]   Review of solar regeneration methods for liquid desiccant air-conditioning system [J].
Cheng, Qing ;
Zhang, Xiaosong .
ENERGY AND BUILDINGS, 2013, 67 :426-433
[6]   Vacuum membrane distillation processes for aqueous solution treatment-A review [J].
Chiam, Chel-Ken ;
Sarbatly, Rosalam .
CHEMICAL ENGINEERING AND PROCESSING-PROCESS INTENSIFICATION, 2013, 74 :27-54
[7]   Experimental study on the performance of membrane based multi-effect dehumidifier regenerator powered by solar energy [J].
Choo, F. H. ;
KumJa, M. ;
Zhao, K. ;
Chakraborty, A. ;
Dass, E. T. M. ;
Prabu, M. ;
Li, B. ;
Dubey, S. .
PROCEEDINGS OF THE 2ND INTERNATIONAL CONFERENCE ON SOLAR HEATING AND COOLING FOR BUILDINGS AND INDUSTRY (SHC 2013), 2014, 48 :535-542
[8]   Membrane distillation: Recent developments and perspectives [J].
Drioli, Enrico ;
Ali, Aamer ;
Macedonio, Francesca .
DESALINATION, 2015, 356 :56-84
[9]   Membrane distillation to regenerate different liquid desiccant solutions for air conditioning [J].
Duong, Hung C. ;
Alvarez, Ivan R. C. ;
Nguyen, Tinh V. ;
Nghiem, Long D. .
DESALINATION, 2018, 443 :137-142
[10]   Liquid desiccant lithium chloride regeneration by membrane distillation for air conditioning [J].
Duong, Hung C. ;
Hai, Faisal I. ;
Al-Jubainawi, Ali ;
Ma, Zhenjun ;
He, Tao ;
Nghiem, Long D. .
SEPARATION AND PURIFICATION TECHNOLOGY, 2017, 177 :121-128