Short-Circuit Current Calculation and Harmonic Characteristic Analysis for a Doubly-Fed Induction Generator Wind Turbine under Converter Control

被引:10
作者
Li, Jing [1 ]
Zheng, Tao [1 ]
Wang, Zengping [1 ]
机构
[1] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewabl, Beijing 102206, Peoples R China
关键词
doubly-fed generator; converter control; short-circuit current; second harmonic component; low-voltage ride-through (LVRT) field test data; DFIG;
D O I
10.3390/en11092471
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
An accurate calculation of short-circuit current (SCC) is very important for relay protection setting and optimization design of electrical equipment. The short-circuit current for a doubly-fed induction generator wind turbine (DFIG-WT) under excitation regulation of a converter contains the stator current and grid-side converter (GSC) current. The transient characteristics of GSC current are controlled by double closed-loops of the converter and influenced by fluctuations of direct current (DC) bus voltage, which is characterized as high order, multiple variables, and strong coupling, resulting in great difficulty with analysis. Existing studies are mainly focused on the stator current, neglecting or only considering the steady-state short-circuit current of GSC, resulting in errors in the short-circuit calculation of DFIG-WT. This paper constructs a DFIG-WT total current analytical model involving GSC current. Based on Fourier decomposition of switch functions and the frequency domain analytical method, the fluctuation of DC bus voltage is considered and described in detail. With the proposed DFIG-WT short-circuit current analytical model, the generation mechanism and evolution law of harmonic components are revealed quantitatively, especially the second harmonic component, which has a great influence on transformer protection. The accuracies of the theoretical analysis and mathematical model are verified by comparing calculation results with simulation results and low-voltage ride-through (LVRT) field test data of a real DFIG.
引用
收藏
页数:23
相关论文
共 27 条
  • [21] Fault Current Characteristics of the DFIG under Asymmetrical Fault Conditions
    Xiao, Fan
    Zhang, Zhe
    Yin, Xianggen
    [J]. ENERGIES, 2015, 8 (10) : 10971 - 10992
  • [22] Analysis of the control limit for rotor-side converter of doubly fed induction generator-based wind energy conversion system under various voltage dips
    Xiao, Shuai
    Geng, Hua
    Zhou, Honglin
    Yang, Geng
    [J]. IET RENEWABLE POWER GENERATION, 2013, 7 (01) : 71 - 81
  • [23] Yin J., 2015, T CHINA ELECT TECH, V30, P118
  • [24] Short-Circuit Current Analysis for DFIG Wind Farm Considering the Action of a Crowbar
    Yuan, Yan Hong
    Wu, Feng
    [J]. ENERGIES, 2018, 11 (02)
  • [25] Zhang C. W., 2003, PWM RECTIFIER CONTRO, P114
  • [26] Three-Phase Short-Circuit Current Calculation of Power Systems with High Penetration of VSC-Based Renewable Energy
    Zhou, Niancheng
    Wu, Jiafang
    Wang, Qianggang
    [J]. ENERGIES, 2018, 11 (03):
  • [27] Equivalent Modeling of DFIG-Based Wind Power Plant Considering Crowbar Protection
    Zhu, Qianlong
    Ding, Ming
    Han, Pingping
    [J]. MATHEMATICAL PROBLEMS IN ENGINEERING, 2016, 2016