Winding Deformation Analysis in Power Transformers using Finite Element Method

被引:0
|
作者
Sahoo, Saroja Kanti [1 ]
Gopalakrishna, S. [2 ]
机构
[1] Indian Inst Technol, Dept Elect Engn, Kharagpur 721302, W Bengal, India
[2] Natl Inst Technol, Dept Elect Engn, Rourkela 769008, India
关键词
Deformation; Frequency response; Natural frequency; Power Transformer; Resonance; Transfer function;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Winding deformation in power transformers affects its mechanical integrity. Diagnosis of winding deformation is a necessary step towards preventing its permanent failure. Sweep Frequency Response Analysis (SFRA) is widely used to analyze the nature and extent of deformation. However, the location of deformation needs the signature from the deformed transformer at various locations, which is practically not feasible. In this paper, Finite Element Method (FEM) and SFRA are used to model deformations on a benchmark winding and obtain corresponding signatures. Different parameters derived from SFRA are used as indices to distinguish type and location of deformations.
引用
收藏
页码:341 / 346
页数:6
相关论文
共 50 条
  • [1] Analysis of Winding Vibration Characteristics of Power Transformers Based on the Finite-Element Method
    Duan, Xiaomu
    Zhao, Tong
    Liu, Jinxin
    Zhang, Li
    Zou, Liang
    ENERGIES, 2018, 11 (09)
  • [2] Analysis of internal winding short circuit faults in power transformers using transient finite element method coupling with external circuit equations
    Behjat, Vahid
    Vahedi, Abolfazl
    INTERNATIONAL JOURNAL OF NUMERICAL MODELLING-ELECTRONIC NETWORKS DEVICES AND FIELDS, 2013, 26 (05) : 425 - 442
  • [3] An On-line Monitoring Method for Winding Deformation of Power Transformers
    Liu, Xing-ping
    Chen, Min-you
    PROCEEDINGS OF THE 2013 IEEE 8TH CONFERENCE ON INDUSTRIAL ELECTRONICS AND APPLICATIONS (ICIEA), 2013, : 255 - 260
  • [4] Finite element analysis of internal winding faults in distribution transformers
    Wang, H
    Butler, KL
    IEEE TRANSACTIONS ON POWER DELIVERY, 2001, 16 (03) : 422 - 428
  • [5] Detection of Minor Axial Winding Movement within Power Transformers Using Finite Element Modeling
    Zhang, Z. W.
    Tang, W. H.
    Wu, Q. H.
    Yan, J. D.
    2014 IEEE PES GENERAL MEETING - CONFERENCE & EXPOSITION, 2014,
  • [6] Research of transformer winding deformation based on Finite Element Method
    Yuan, J.
    Yuan, J.
    Yu, Z.
    2015 IEEE MAGNETICS CONFERENCE (INTERMAG), 2015,
  • [7] Simulative research on frequency response to winding deformation of power transformer based on finite element method
    Zou L.
    Liao Y.
    Luo B.
    Zhao Z.
    Chen X.
    Yao C.
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2017, 37 (01): : 204 - 211
  • [8] The analysis of mechanical strength of hv winding using finite element method, Part II - Mechanical stress and deformation analysis
    Meng, ZQ
    Wang, ZD
    UPEC 2004: 39TH INTERNATIONAL UNIVERSITITIES POWER ENGINEERING CONFERENCE, VOLS 1-3, CONFERENCE PROCEEDINGS, 2005, : 183 - 187
  • [9] Analysis of Stray Losses in Transformers using Finite Element Method Modelling
    Thango, Bonginkosi A.
    Jordaan, Jacobus A.
    Nnachi, Agha F.
    2021 IEEE PES/IAS POWERAFRICA CONFERENCE, 2021, : 41 - 45
  • [10] Sensitive method for detection of winding deformation in transformers
    Gopalakrishna, S.
    Ilampoornan, M. K.
    Jayashankar, V.
    ISEIM 2008: PROCEEDINGS OF 2008 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING, 2008, : 56 - 56